Viconics VT7606E Installation Manual User Manual
Page 12

12
| PIR Ready VT7600 Series-Installation Guide
028-0363-02
When left unattended for 45 seconds, the display will resume automatic status display
scrolling.
To turn on the back light, press any key on the front panel. The back lit display will turn
off when the Terminal Equipment Controller is left unattended for 45 seconds
Sequence of user menu:
OVERRIDE
RESUME
SYSTEM MODE
SETTING
SCHEDULES
SETTING
CLOCK
SETTING
Override schd
Y/N
Sys mode set
Y/N
Schedule set
Y/N
Clock set
Y/N
Appears only
in unoccupied
mode
Cancel ovrd
Y/N
Appears only
in override
mode
A) Override an unoccupied period
Override
schd Y/N
This menu will appear only when the Terminal Equipment Controller is in unoccupied
mode.
Answering yes to this prompt will cause the Terminal Equipment Controller to go into
occupied mode for an amount of time equal to the parameter “TOccTime” (1 to 12
hours).
B) Resume regular scheduling
Cancel
ovrd Y/N
This menu does not appear in regular operation. It will appear only when the Terminal
Equipment Controller is in Unoccupied override mode.
Answering “Yes” to this question will cause the Terminal Equipment Controller to
resume the regular setpoints & scheduling.
C) Temperature setpoints
Permanent setpoint changes
Temperat
set Y/N
This menu permits the adjustment of all permanent temperature setpoints (occupied
and unoccupied) as well as the desired temperature units (°F or °C). Permanent
setpoints are written to RAM and EEPROM.