Viconics VT7606E Installation Manual User Manual
Page 23
23
| PIR Ready VT7600 Series-Installation Guide
028-0363-02
Cool cph
Cooling stages cycles
per hour Default value =
4 C.P.H.
Will set the maximum number of cooling stage cycles
per hour under normal control operation. It represents
the maximum number of cycles that the equipment will
turned on and off in one hour.
Note that a higher C.P.H will represent a higher accuracy
of control at the expense of wearing mechanical compo-
nents faster.
3 or 4 C.P.H.
For multi stage models, cool cph applies to Y1 & Y2
For heat pump models, cool cph applies to Y1 &
Y2 in cooling and heating independently of the
reversing valve position
Deadband
Minimum deadband
Default value =
2.0 °F
(1.1 °C)
The minimum deadband value between the heating and
cooling setpoints. When modified, it will take effect only
when any of the setpoints are modified again.
Range is:
2, 3, or 4 °F, 1.0 °F increments (1.0 to 2.0 °C,
0.5 °C increments)
Fan cont
Fan control
Default value =
On
Fan control in heating mode.
When selecting On; the Terminal Equipment Controller in
all cases will always control the fan (terminal G).
Valid for On or Auto fan mode
When selecting Off; the fan (terminal G), when heating
stages (terminals W1 & W2) are solicited, will not be
energized. The fan in this case will be controlled by the
equipment fan limit control.
Valid only for Auto fan mode. On fan mode will leave the
fan always on.
ON OR OFF
For multi stage models, fan control applies to W1 &
W2
For heat pump models, fan control applies to W1
only (Emergency heat)
Fan del
Fan delay
Default value =
Off
Fan delay extends fan operation by 60 seconds after the
call for heating or cooling ends.
Valid only for Auto fan mode. “On” fan mode will leave
the fan always on.
Off or On
TOccTime
Temporary occupancy
time
Default value =
2 hours
Temporary occupancy time with occupied mode setpoints
when override function is enabled.
When the Terminal Equipment Controller is in unoccu-
pied mode, function is enabled with either the menu or
UI2 configured as remote override input.
Range is:
0,1, 2, 3, 4, 5, 6, 7, 8, 9, 10, & up to 24 hours
Cal RS
Room temperature
sensor calibration
Default value =
0.0 °F
or °C
Offset that can be added/subtracted to the actual dis-
played room temperature
± 5.0 °F, (± 2.5 °C)