| PIR Ready VT7600 Series-Installation Guide

028-0363-02

Min Pos
Minimum Fresh Air

Damper/Economizer

Position
Default value =

0%

Minimum fresh air damper position. Effective only in

Occupied mode (Fan is ON). This value is also used to

determine the fresh air damper position based on the

Min/Max CO

2

and Min/Max Pos values set. See Fresh Air

Damper Position section for more details.
0% to 100%, 1 or 10 increments

Max Pos
Maximum Fresh Air

Damper/Economizer

Position
Default value =

100%

Maximum fresh air damper position. Effective only in Oc-

cupied mode (Fan is ON). This value is used to deter-

mine the fresh air damper position based on the Min/Max

CO

2

and Min/Max Pos values set. See Fresh Air Damper

Position section for more details.
0% to 100%, 1 or 10 increments

Min FA

Minimum Fresh Air

Value

Default value =

0 CFM

Minimum fresh air required. Effective only in Occupied

mode (Fan is ON). This value is used to determine the

fresh air damper position based on the Min/Max CO

2

and

Min/Max FA values (if FA Range is set to other than 0

CFM). See Fresh Air Damper Position section for more

details.

0 to 20 000 CFM (0 to 9438 L/s) (the value set cannot

exceed the value of FA Range parameter), 10 or 100

increments

Max FA

Maximum Fresh Air

Value

Default value =

0 CFM

Maximum fresh air allowed. Effective only in Occupied

mode (Fan is ON). This value is used to determine the

fresh air damper position based on the Min/Max CO

2

and

Min/Max FA values set (if FA Range is set to other than

0 CFM). See Fresh Air Damper Position section for more

details.

0 to 20 000 CFM (0 to 9438 L/s) (the value set cannot

exceed the value of FA Range parameter), 10 or 100

increments

Min CO

2

Minimum CO

2

Level

Default value =

800

ppm

Minimum CO

2

Level required. Effective only in Occupied

mode (Fan is ON). This value is used to determine the

fresh air damper position based on the Min/Max CO

2

and

Min/Max Pos values set. See Fresh Air Damper Position

section for more details.

0 to 2000 ppm, 10 or 100 increments