Table 15 — Troubleshooting (cont)

LEGEND

FAULT

HEATING

COOLING

POSSIBLE CAUSE

SOLUTION

Only Compressor Runs

X

X

Thermostat wiring

Check G wiring at heat pump. Jumper G and R for fan operation.
Check Y and W wiring at heat pump. Jumper Y and R for compressor
operation in Test mode.

X

X

Fan motor relay

Jumper G and R for fan operation. Check for line voltage across BR
contacts.
Check fan power enable relay operation (if present).

X

X

Fan motor

Check for line voltage at motor. Check capacitor.

Unit Does Not Operate in
Cooling

X

Reversing valve

Set for cooling demand and check 24-vac on RV coil and at control.
If RV is stuck, run high pressure up by reducing water flow and while
operating engage and disengage RV coil voltage to push valve.

X

Thermostat setup

Check for ‘O’ RV setup not ‘B’.

X

Thermostat wiring

Check O wiring at heat pump. Jumper O and R for RV coil.

Insufficient Capacity/
Not Cooling or Heating
Properly

X

X

Dirty filter

Replace or clean.

X

Reduced or no airflow in
heating

Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
High external static. Check duct design and downstream interference.

X

Reduced or no airflow in
cooling

Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
High external static. Check duct design and downstream interference.

X

X

Leaky ductwork

Check supply and return-air temperatures at the unit and at distant
duct registers if significantly different, duct leaks are present.

X

X

Low refrigerant charge

Check superheat and subcooling.

X

X

Restricted metering device

Check superheat and subcooling. Replace.

X

Defective reversing valve

Perform RV touch test.

X

X

Thermostat improperly
located

Check location and for air drafts behind thermostat.

X

X

Unit undersized

Recheck loads and sizing check sensible cooling load and heat pump
capacity.

X

X

Scaling in water heat
exchanger

Perform scaling check and clean if necessary.

X

X

Inlet water too hot or cold

Check load, loop sizing, loop backfill, ground moisture.

High Head Pressure

X

Reduced or no airflow in
heating

Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
High external static. Check duct design and downstream interference.

X

Reduced or no water flow in
cooling

Check pump operation or valve operation/setting.
Check water flow adjust to proper flow rate.

X

Inlet water too hot

Check load, loop sizing, loop backfill, ground moisture.

X

Air temperature out of range
in heating

Bring return-air temperature within design parameters.

X

Scaling in water heat
exchanger

Perform scaling check and clean if necessary.

X

X

Unit overcharged

Check superheat and subcooling. Reweigh in charge.

X

X

Non-condensables in
system

Vacuum system and reweigh in charge.

X

X

Restricted metering device

Check superheat and subcooling. Replace.

Low Suction Pressure

X

Reduced water flow in
heating

Check pump operation or water valve operation/setting.
Plugged strainer or filter. Clean or replace.
Check water flow adjust to proper flow rate.

X

Water temperature out of
range

Bring water temperature within design parameters.

X

Reduced airflow in cooling

Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
High external static. Check duct design and downstream interference.

X

Air temperature out of range Too much cold vent air. Bring entering air temperature within design

parameters.

X

X

Insufficient charge

Check for refrigerant leaks.

Low Discharge Air
Temperature in Heating

X

Too high airflow

Check blower.

X

Poor performance

See ‘Insufficient Capacity’ above.

High Humidity

X

Too high airflow

Check blower.

X

Unit oversized

Recheck loads and sizing check sensible cooling load and heat pump
capacity.