Fig. 21 — 50PEC Unit Remote-Mounted Thermostat with Complete C Controller Wiring

Complete C

Complete C

AL

Alarm Relay Contacts

BM

Blower Motor

BR

Blower Relay

CAP

Capacitor

CB

Circuit Breaker

CO

Sensor, Condensate Overflow

CR

Compressor Relay

DM

Damper Motor

ES

End Switch

FP1

Sensor, Water Coil Freeze Protection

FP2

Sensor, Air Coil Freeze Protection

FSS

Fan Speed Switch

HPS

High-Pressure Switch

HPWS

High-Pressure Water Switch

JW1

Jumper Wire for Alarm

LOC

Loss of Charge Pressure Switch

PDB

Power Distribution Block

RVS

Reversing Valve Solenoid

TRANS —

Transformer

WV

Water Valve

----------

Field Line Voltage Wiring
Field Low-Voltage Wiring

LEGEND

Printed Circuit Trace
Option Low Voltage
Wiring

Relay/Contactor Coil

Solenoid Coil

Thermistor

Circuit Breaker

Relay Contacts-N.O.

Switch-High Pressure

Switch-Low Pressure

Ground

Wire Nut

Mate-N-Lock

>>

*Optional wiring.

NOTES:

1. Compressor and blower motor thermally pro-

tected internally.

2. All wiring to the unit must comply with local

codes.

3. Transformer is wired to 240-V (ORG) lead for

240-1-50 units. For 220-1-50 operation, switch
the RED and ORG leads at L1 and insulate the
RED lead. Transformer is energy limiting or may
have a circuit breaker.

4. FP1 thermistor provides freeze protection for

water. When using anti-freeze solutions, cut
JW3 jumper.

5. Low voltage wiring must be class 1 and voltage

rated equal or greater than unit supply voltage.

6. Factory cut jumper (JW1). Dry contact will be

available between AL1 and AL2.

7. Transformer secondary ground via GRN/YEL

wire from C to control box.

8. See view A for wiring of units with water valve

(part no. 23B00112N01) or view B for units with
water valve (part no. 23B00112N03).