beautypg.com

Carrier 50PEC09-18 User Manual

Page 26

background image

26

OPTIONAL WALL-MOUNTED THERMOSTAT —

The 50PEC water source heat pump units are built with stan-

dard internal thermostats in either manual changeover (MCO)

or automatic changeover (ACO) configuration. Refer to

Fig. 17-20.

When desired, the unit can be furnished with a 24-v control

circuit which is field wired to a Carrier-supplied accessory re-

mote thermostat. Most heat pump thermostats can be used with

the controller. Use a thermostat with Y, G, O and W outputs.

Refer to unit wiring diagrams in Fig. 21 and 22 and Aqua-

zone™ Controls, Operation, and Troubleshooting Instructions

for additional information.

Vendor installation instructions and additional installation

information is shipped with each thermostat.
NOTE: Low-voltage wiring between the unit and the wall ther-

mostat must comply with all applicable electrical codes

(i.e., NEC and local codes), and be completed before the unit is

installed.

Table 3 lists recommended wire sizes and lengths to install

the thermostat. The total resistance of low-voltage wiring must

not exceed 1 ohm. Any resistance in excess of 1 ohm may

cause the control to malfunction because of high voltage drop.

Table 3 — Recommended Thermostat Wire Sizes

*Length = Physical distance from thermostat to unit.

OPTIONAL PREMIERLINK™ CONTROLLER — This

direct digital controller (DDC) allows the water source heat

pump to be incorporated into a Carrier Comfort Network

®

(CCN) system installation. PremierLink control is factory-

installed with the Complete C controller, or field-installed with

the Deluxe D control option. Refer to Fig. 23 and 24.

Step 6 — Install Supply and Return Piping

SUPPLY AND RETURN HOSES — Optional pressure-rated

hose assemblies are available for use with units. Use the fol-

lowing guidelines when installing supply and return hose

assemblies.

1. Install supply and return hoses fitted with swivel-joint

fittings at one end to prevent the hose from twisting.

2. Use male adapters to secure the hose assembly to the unit

and the riser.

3. Do not allow the hose to twist during installation. Twist-

ing may damage the hose wall or the rubber compound.

4. Use pipe joint compound sparingly on the fitting adapt-

ers’ male pipe threads.

5. Prevent sealant from reaching the joint’s flared surfaces.

6. Do not use pipe joint compound when Teflon* thread

tape is pre-applied to hose assemblies or when flared-end

connections are used.

7. Maximum torque that may be applied to brass fittings is

40 N

m. When a torque wrench is not used, tighten brass

fittings finger-tight plus one quarter turn.

8. Tighten steel fittings as necessary.

9. Use shut-off/balancing valves, flow indicators, and drain

tees in the supply runout and return at each floor to aid in

loop balancing and servicing.

SUPPLY AND RETURN PIPING — System piping MUST

comply with all applicable codes.

1. Install a drain valve at the base of each supply and return

riser to enable system flushing at start-up and during rou-

tine servicing.

2. Install shut-off/balancing valves and unions at each unit

to allow unit removal for servicing.

NOTE: If flex hoses are used, unions are not necessary.

3. Install strainers at the inlet of each system circulating

pump.

4. Before making the final water connections, flush the sys-

tem as described in the Pre-Start-Up section of this

manual. After flushing the system, connect piping and

hoses to the proper supply, return and condensate connec-

tions of the unit.

NOTE: When necessary, use adapters to connect hoses.

5. Install any other system components, as required, follow-

ing manufacturer’s instructions.

6. Reinstall the front cabinet by carefully lowering the front

cabinet over the chassis onto the backplate.

Step 7 — Install Condensate Piping —

Connect

the unit condensate drain to the building condensate drain with

a flexible, nonpressure-rated

5

/

8

-in. (16 mm) ID plastic hose.

Avoid kinks in this hose to ensure an unobstructed flow of con-

densate from the unit to the drain.

The horizontal run of the condensate hose is usually too

short to pose any drainage problems, however, the horizontal

run of condensate line should be pitched at least 10 mm for ev-

ery 1 m of run (in the direction of flow). Avoid low points and

unpitched piping since dirt collects in these areas and may

cause stoppage and overflow.

Field installation of a trap or vent is not required unless

specified by local codes. The 50PEC units are designed in a

blow-thru configuration. The condensate drain pan is located

on the outlet side of the blower so that the pressure in the drain

pan is higher than the atmospheric pressure.

WIRE SIZE

MAX WIRE LENGTH*

18-Gage

20 m

16-Gage

35 m

14-Gage

60 m

CAUTION

To ensure proper functioning of unit and system, be sure to

connect entering water to upper pipe on right-hand units.

On left-hand units, connect entering water to lower pipe.

Failure to do so could result in equipment damage.

Fig. 28 — Taco SBV Valve Wiring

a50-8442

IMPORTANT: Since loop temperatures are normally

between 15.6 C and 32.2 C, pipe sweating and heat loss do

not occur at normal ambient temperature conditions. Insu-

lation must be installed on loop water piping on those sec-

tions that run through unheated areas or are located outside

the building. If loop temperatures are expected below the

ambient dew point, the optional internal insulation

(extended range) package must be ordered.

CAUTION

DO NOT bend or kink supply lines or hoses. Damage to

unit may result.

* Registered trademark of DuPont.