Model 5128/29 Fire Slave Communicator Installation Manual

4

150805

2.2

FCC Warning

2.3

UL Listings and Requirements

All UL installations must comply with the requirements described below. Refer to the control unit’s installation
manual for complete information.
5128 Requirements:
The 5128 must be mounted within a UL listed compatible fire control panel.
5129 Requirements:
The 5129 and the UL listed compatible fire control must be installed in the same room. All wiring between the
5129 and the UL Listed compatible fire control panel must be enclosed in conduit. The 5129 must be mounted
within 20 feet of the fire control.
Requirements for both 5128 and 5129:
All electrical connections must comply with the ratings shown in section 3.3.5. In a remote signaling
installation, the control unit, slave dialer, and receiver at the remote site must all be UL listed for remote
signaling.
Install in accordance with NFPA 70 and NFPA 72.

WARNING:

This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions: (1) This device may
not cause radio interference, and (2) This device must accept any interference received, including interference that may cause
undesired operation.

Model

Listed As:

5128

Signaling device subassembly for use in Fire Alarm Systems for Central
Station Service.
Signaling device subassembly for use in Remote Supervising Fire Alarm
Systems.

5129

Signaling device for use in Fire Alarm Systems for Central Station Service.
Signaling device for use in Remote Supervising Fire Alarm Systems.