Model 5128/29 Fire Slave Communicator Installation Manual
20
150805
S
ECTION
5
P
ROGRAMMING
The Model 5128/29 provides a wide variety of features that can be selected for use depending on your needs.
These features are stored in an EEPROM (Electrically Erasable Programmable Read-Only Memory) chip
which has been factory-programmed. Section 5.1 describes how to change programming options using the
5230 Remote Annunciator. The 5230 Remote Annunciator is required for all programming changes. Section
5.2 explains using the Model 5541 Downloading Software for programming. All programmable options are
described in Section 5.3.
5.1 UL 864 Programming Requirements
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING
JURISDICTION, AND OTHER INVOLVED PARTIES: This product
incorporates field programmable software. In order for the product to comply
with the requirements in the Standard for Control Units and Accessories for
Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.
Programming Option
Permitted in
UL 864 (Y/N)
Possible
Settings
Settings Permitted in
UL 864
AC Loss Hours
Y
0 – 15 hours
1 – 3 hours
Zone Supervised
Y
Y/N
Y
Formats
Y
0–8
0, 5 or 8
Zone Response
Y
0–3
0 or 1
Relay #1
Y
0–2
0 or 1