Model 5128/29 Fire Slave Communicator Installation Manual

20

150805

S

ECTION

5

P

ROGRAMMING

The Model 5128/29 provides a wide variety of features that can be selected for use depending on your needs.
These features are stored in an EEPROM (Electrically Erasable Programmable Read-Only Memory) chip
which has been factory-programmed. Section 5.1 describes how to change programming options using the
5230 Remote Annunciator. The 5230 Remote Annunciator is required for all programming changes. Section
5.2 explains using the Model 5541 Downloading Software for programming. All programmable options are
described in Section 5.3.

5.1 UL 864 Programming Requirements

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING

JURISDICTION, AND OTHER INVOLVED PARTIES: This product

incorporates field programmable software. In order for the product to comply

with the requirements in the Standard for Control Units and Accessories for

Fire Alarm Systems, UL 864, certain programming features or options must be

limited to specific values or not used at all as indicated below.

Programming Option

Permitted in

UL 864 (Y/N)

Possible

Settings

Settings Permitted in

UL 864

AC Loss Hours

Y

0 – 15 hours

1 – 3 hours

Zone Supervised

Y

Y/N

Y

Formats

Y

0–8

0, 5 or 8

Zone Response

Y

0–3

0 or 1

Relay #1

Y

0–2

0 or 1