NOTES FOR STEPS 8-11:
Channel response time speeds are not intended to be used as a smoke verification feature. Possible choices for channel response times are
0-3 (described below).
8
System
Menu
ZONE RESPONSE #1
0 = 0.3 to 0.4 seconds 1 = 3 to 4 seconds
2 = 15 to 20 seconds 3 = 30 to 40 seconds
NOTE: If you make a mistake and program a number other than 0-3, the
resulting zone speed will be:
4 = 0.3 to 0.4 seconds 5 = 3 to 4 seconds
6 = 15 to 20 seconds 7 = 30 to 40 seconds
8 = 0.3 to 0.4 seconds
9 = 3 to 4 seconds
0.3 to 0.4 sec (D)
3 to 4 sec
15 to 20 sec
30 to 40 sec
9
System
Menu
ZONE RESPONSE #2
Factory programmed as “1” (3 to 4 seconds). Cannot be changed.
No selection.
10
System
Menu
ZONE RESPONSE #3
(See step 8.)
0.3 to 0.4 sec (D)
3 to 4 sec
15 to 20 sec
30 to 40 sec
11
System
Menu
ZONE RESPONSE #4
(See step 8.)
0.3 to 0.4 sec (D)
3 to 4 sec
15 to 20 sec
30 to 40 sec
12
System
Menu
RELAY #1
0 = Relay activates on alarm
1 = Relay activates on system trouble
2 = Relay activates on system trouble excluding Low AC
Alarm
Trouble
Trouble excluding
low AC (D)
13
System
Menu
INSTALLER’S CODE
Installer’s code [4 digits]. For programming and other system control
functions. Can also perform all the same operations as the operator’s code.
(See Section 4.2 for specific information about which functions the code
can perform.)
________________
Default = 5128
14
Dialer
Menu
OPERATOR’S CODE
Operator’s code [4 digits]. Used for basic operation. (See Section 4.2 for
specific information about which functions the code can perform.) This
code must be different from the installer’s code.
________________
Default = 1111
15
Dialer
Menu
DIALER TYPE
0 = USA
1 = 9000 Direct (Do not use this option.)
2 = European (used for Europe and Asia)
USA (D)
European
Table 5-2: Programming Form
Step # /
From
Menu
Option
Description
Your Choice
(D) = Default