The Silent Knight Model 5128/29 is a low-cost slave communicator that meets the requirements for UL 864,
NFPA 72 Fire Alarm Systems for Central Station Service and NFPA 72 Remote Supervising Station Fire
Alarm Systems.

1.1

Features

Compatibility with the Security Industry Association (SIA) reporting format and several other standard
reporting formats.

Four channel (zone) inputs for system status reporting: fire alarm (channel or zone 1); system trouble–
channel 2 (or zone 2); supervisory–channel 3 (or zone 3); and miscellaneous–channel 4 (or zone 4).

Optional two-number dialing with same or different account codes and reporting formats. Alarms,
troubles, and tests can be programmed to be reported to either or both numbers.

Programmable as rotary-only or as Touch-Tone/rotary dialing.

Built-in dual phone line-seizure circuit.

Dual phone line monitor circuits.

Transient voltage protection of phone lines.

Built-in audible trouble buzzer.

One relay output, programmable for alarm, trouble conditions, or trouble excluding low AC.

Light-emitting diodes (LEDs), visible from front of enclosure, indicating: trouble condition (yellow);
presence of DC power (green), phone line 1 trouble (red); and phone line 2 trouble (red).

Easy, English-language programming using Model 5230 Remote Annunciator.

Fuseless design, 24 VDC.

Electrically erasable read-only memory (EEPROM) for nonvolatile storage of all programmable option
data. Eliminates the need to reprogram the communicator if power is lost.

Built-in watchdog circuit that monitors the operation of the 5128/29 and resets the communicator if a fault
is detected.

Active high or contact closure input.

Model 5129 can directly monitor control panel’s primary power.

Compatibility with many Underwriters Laboratories (UL) Fire Listed receivers. (See Section 1.3 for list.)

Model 5128 housed in 8-5/8" x 4" x 1-3/8" enclosure for mounting inside control panel.

Model 5129 housed in a 10" x 10" metal enclosure.