beautypg.com

Warning – Reznor P6SP Unit Installation Manual User Manual

Page 8

background image

8

1. Measure the line voltages

of your 3-phase power

supply where it enters the

building and at a location

that will only be dedicated

to the unit installation. (at

the units circuit protection

or disconnect).

Example

:

AB = 451V

BC = 460V

AC = 453V

In this example, the measured line voltages were

451, 460, and 453. The average would be 454 volts

(451 + 460 + 453 = 1,364 / 3 = 454).

Example:

From the values given in step 1, the BC voltage (460V)

is the greatest difference in value from the average:

460 - 454 = 6

454 - 451 = 3

454 - 453 = 1

Highest Value

max voltage deviation

from average voltage

= 100 x

average voltage

% Voltage Imbalance

6

454

100 x

= 1.32%

Example:

unit. Use proper code agency listed conduit and a conduit

connector for connecting the supply wires to the unit and

for obtaining proper grounding. Grounding may also be

accomplished by using the grounding lug provided in the

control box.

Low Voltage Connections - Thermostat

A two stage cooling 24 VAC thermostat is required for

these units. Several options are available for a room

thermostat depending on the accessories installed with

the unit. Select a thermostat which operates in conjunction

with the installed accessories. The thermostat should be

mounted about five feet above the floor on an inside wall.

The thermostat should be kept away from drafts, slamming

doors, lamps, direct sunlight and the supply air flow.

To install the thermostat:

1. Position the subbase on an inside wall and mark the

mounting holes and thermostat cable openings.

2. Cut out the cable opening and route the thermostat

cable from the unit’s low voltage compartment to the

thermostat location. The thermostat cable is supplied

by the installer. See Figure 8 for recommended wire

size.

3. Connect the cable leads to the subbase or thermostat

terminals and to the unit’s low voltage terminal block

as shown in Figure 8. System wiring diagrams are also

provided on the inside of the control access panel and

in Figures 13 - 16 (pages 21 - 22).

4. Secure the subbase or thermostat to the wall using

screws provided with the thermostat.

5. Install the correct thermostat housing to subbase.

6. Refer to thermostat instruction sheet for complete

detailed mounting and operating information.

3. Determine the maximum deviation: See example.

2. Determine the average voltage in the power supply.

Figure 8. typical connections -

2 stage cool / 1 stage Heat t-stat

Y1

Y2

W

1

/E

G

RH

RC

Y1

Y2

W

1

/E

G

R

Indoor Thermostat

Sub-Base

Unit Low Voltage

Terminal

24 V Hot

Blower

Emer. Heat

Stage 2
Heat/Cool

Stage 1
Heat/Cool

24 V Com

C

C

t-stat Wire

Gauge

recommended t-stat Wire

length - Ft. (unit to t-stat)

18 Ga.

0 - 60

16 Ga.

61 - 130

Field Supplied Wiring - - - - - Use Solid Class II Copper Wire

notE: If thermostat has one combined “O/B” Terminal and an
Economizer is installed, see Economizer Installation Instructions for
unit wiring change for proper operation.

4. Determine percent of

voltage imbalance by

using the results from

steps 2 & 3 in the following

equation.

The amount of phase imbalance (1.32%) is satisfactory

since the amount is lower than the maximum allowable

2%. Please contact your local electric utility company if

your voltage imbalance is more than 2%.

Grounding

WarnInG:

the unit cabinet must have an uninterrupted or

unbroken electrical ground to minimize personal
injury if an electrical fault should occur. Do not
use gas piping as an electrical ground

!

This unit must be electrically grounded in accordance

with local codes or, in the absence of local codes, with

the National Electrical Code (ANSI/NFPA 70) or the CSA
C22.1 Electrical Code. Use the grounding lug provided in
the element access compartment for grounding the unit.

Line Voltage Connections

Provide power supply for the unit in accordance with the

unit wiring diagram, and the unit rating plate. Connect

the line-voltage leads to the corresponding terminals on

the terminal block inside the control compartment. Use

only copper wire for the line voltage power supply to this