P6sp-090(c/d)a – Reznor P6SP Unit Installation Manual User Manual
Page 27

27
P6sP-090(c/D)a
Factory Standard: 1.5Hp Horizontal Performance Chart
‡ Indicates Factory Sheave Setting for Pre-configured Units
External
Unit
Static
(in-Wg)
Operating
@ 230 or
460 Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2
Turn
Open
1
Turn
Open
1.5
Turns
Open
2
Turns
Open
2.5
Turns
Open
3
Turns
Open
3.5
Turns
Open
4
Turns
Open
4.5
Turns
Open ‡
5
Turns
Open
5.5
Turns
Open
6
Turns
Open
0.1
CFM
3722
3610
3496
3382
3263
3143
RPM
889
864
844
824
799
773
kW
1.52
1.39
1.29
1.19
1.09
0.99
0.2
CFM
3695
3577
3458
3338
3217
3094
2970
RPM
917
893
869
847
825
800
775
kW
1.57
1.45
1.32
1.23
1.13
1.03
0.93
0.3
CFM
3552
3429
3306
3173
3039
2912
2785
RPM
920
897
873
850
826
801
776
kW
1.48
1.37
1.25
1.15
1.05
0.96
0.86
0.4
CFM
3498
3387
3266
3144
3004
2863
2728
2592
RPM
943
923
899
875
851
828
804
779
kW
1.51
1.41
1.29
1.17
1.08
0.98
0.89
0.80
0.5
CFM
3471
3353
3234
3100
2966
2820
2673
2523
2372
RPM
965
945
925
901
876
853
830
806
782
kW
1.54
1.43
1.32
1.21
1.09
1.00
0.91
0.82
0.73
0.6
CFM
3415
3309
3186
3062
2919
2776
2616
2455
2282
RPM
986
966
947
928
904
879
856
833
809
kW
1.57
1.46
1.34
1.23
1.12
1.01
0.92
0.83
0.74
0.7
CFM
3360
3251
3142
3012
2881
2722
2563
2388
2212
RPM
1010
990
971
951
931
907
882
859
835
kW
1.58
1.47
1.35
1.25
1.15
1.04
0.92
0.83
0.74
0.8
CFM
3211
3091
2970
2828
2686
2505
2323
RPM
1014
994
975
954
934
910
886
kW
1.50
1.38
1.26
1.16
1.05
0.94
0.83
0.9
CFM
3140
3032
2902
2771
2610
2449
2245
RPM
1031
1017
998
978
957
936
913
kW
1.50
1.39
1.28
1.16
1.06
0.96
0.85
1.0
CFM
3069
2954
2842
2700
2557
2369
RPM
1049
1034
1021
1001
981
960
kW
1.52
1.39
1.29
1.17
1.06
0.96
1.1
CFM
2875
2762
2630
2473
2316
RPM
1053
1039
1024
1004
985
kW
1.41
1.29
1.18
1.07
0.96
1.2
CFM
2673
2546
2395
RPM
1058
1044
1028
kW
1.29
1.18
1.06
1.3
CFM
2451
2296
RPM
1062
1048
kW
1.19
1.06
Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil
When utilized with H5HK Heater kits, not all operational points shown may be available for use. Refer to the H5HK Installation
Instructions to determine the minimum airflow requirements of the applicable heater assembly.
Deduct 250 Cfm for electric heater kits
table 8. Blower Performance for P6sP-090(c,D)a series
(7.5 ton Horizontal Models only)