beautypg.com

Warning – Reznor P6SP Unit Installation Manual User Manual

Page 6

background image

6

3” min

Figure 7. concrete Pad Installations

Roof
Curb

Figure 6. roof curb Installations

cIrculatInG aIr suPPlY

WarnInG:

Do not allow combustion products to enter the
return air ductwork or the circulating air supply.
Failure to prevent the circulation of combustion
products into the occupied space can create
potentially hazardous conditions including
carbon monoxide poisoning that could result
in personal injury or death.
all return ductwork must be secured to the
unit with sheet metal screws. all joints must be
taped and adequately sealed. When return air
is provided through the bottom of the unit, the
joint between the unit and the return air plenum
must be air tight.
the roof curb or framing must provide sound
physical support of the unit with no gaps,
cracks, or sagging between the unit and the
curb or frame.
return air and circulating air ductwork must
not be connected to any other heat producing
device such as a fireplace insert, stove, etc. this
may result in fire, explosion, property damage,
personal injury, or death from carbon monoxide
poisoning.

• This unit is designed only for use with a supply and

return duct. Any exterior ducts, joints, or openings in

the building roof or walls must be weatherized with

conventional flashing and sealing compounds.

• Air ducts should be installed in accordance with all

applicable local codes and the standards of the National

Fire Protection Association “Standard for Installation

of Air Conditioning Systems” (NFPA 90A).

• Design the ductwork according to methods described

by the Air Conditioning Contractors of America (ACCA)

Manual Q.

• It is recommended that the outlet duct be equipped

with a removable access panel. This opening should

be accessible when the unit is installed in service and

shall be of a size such that the smoke or reflected light

may be observed inside the casing to indicate the

presence of leaks in the heat exchanger. The cover for

the opening shall be attached in such a manner as to

prevent leaks.

• If outside air is used as return air for ventilation or to

improve indoor air quality, the system must be designed

so that the return air to the unit is not less than 50° F

(10° C) during heating operation. If a combination of

indoor and outdoor air is used, the ducts and damper

system must be designed so that the return air supply

to the unit is equal to the return air supply under normal,

indoor return air applications.

must be square and level to ensure proper condensate

drainage. Unit clearances must be in accordance with

those shown in Figure 1 (page 4).

unconditioned spaces

All ductwork passing through unconditioned spaces

must be properly insulated to minimize duct losses and

prevent condensation. Use insulation with an outer vapor

barrier. Refer to local codes for any insulation material

requirements.