1. Set the thermostat to above room temperature.

2. Verify that the compressor and outdoor fan motor are

not energized and the electric heat is energized.

3. After the unit has run for approximately five minutes,

set the thermostat below room temperature and verify

that the electric heat has de-energized.

WarnInG:

uninsulated live components are exposed when
control access panel is removed.

Verify Operation of Over-Temperature Limit Control

To verify operation of the over-temperature limit control,

make sure that all access panels are in place and that

there is power to the unit. Block the return airflow to the

unit by installing a close-off plate in place of or upstream

of the filter. Set the thermostat to a temperature above

room temperature and verify the unit operates with the

correct operating sequence (see Operating Sequence).

The over-temperature limit control should function to turn

off the electric strip heat within approximately four minutes

notE: the exact time depending on the efficiency of the

close-off in blocking the return air to the unit.

The circulating air blower should continue to run when

the over-temperature limit control switch opens. Remove

the close-off immediately after the over-temperature limit

control opens. If the unit operates for more than four minutes

with no return air, set the thermostat to a temperature

below room temperature, shut off the power to the unit,

and replace the over-temperature limit control.

oPEratInG sEQuEncE

The operating sequences for the heating, cooling, and fan

modes are described below. Refer to the wiring diagrams

for the unit. See pages 21 - 22

cooling mode

1. On a call for cooling the thermostat closes, applying

24 Vac to

Y1, G, and Y2 if stage 2 cooling is required.

2.

G applies 24VAC to the main circulating blower circuit.

3.

Y1 and Y2 apply 24VAC through all safety switches

Before energizing their respective contactors.

4. When the thermostat is satisfied the contactors are

De-energized.

5. The circulating blower motor is de-energized

Immediately.

Blower mode

1. On a call for fan operation, the thermostat applies 24

Vac directly to the blower contactor.

2. The circulating blower is energized immediately.

Heating mode

1. On a call for heat the thermostat closes, applying 24

Vac to the

W1 terminal.

unit Fails to operate

If the unit does not operate properly in either the heating

or cooling mode, be certain to check the following:

1. The thermostat is operating properly.

unIt MaIntEnancE

WarnInG:

to avoid risk of electrical shock, personal
injury, or death, disconnect all electrical power
to the unit before performing any maintenance
or service. the unit may have more than one
electrical supply.

cautIon:

use care when removing parts from this unit.
Personal injury can result from sharp metal
edges present in all equipment of sheet metal
construction.

cautIon:

Verify proper operation after servicing.

refrigerant charging

Packaged electric units are fully charged at the factory.

The system refrigerant charge can be checked and

adjusted through the service ports provided behind the

compressor service panel. Use only gauge lines which

have a “Schrader” depression device present to actuate

the valve. Draw a vacuum on gauge lines to remove

air or moisture before attaching them to the service

ports on the unit. Refrigerant charging must be done by

qualified personnel familiar with safe and environmentally

responsible refrigerant handling procedures. See Unit

Rating Plate for proper amount of charge. See page 30.

WarnInG:

the units are shipped fully charged and ready
for installation. When a system is installed
according to these instructions, no refrigerant
charging is required. If repairs make it necessary
for evacuation and charging, it should only be
done by qualified, trained personnel thoroughly
familiar with this equipment. some local codes
require licensed installation/service personnel
to service this type of equipment. under no
circumstances should the owner attempt to
install and/or service this equipment. Failure
to comply with this warning could result in
property damage, personal injury, or death.

2. Electrical power to the unit is turned on.

3. All safety switches are closed.

4. The service doors are in place.

5. Transformer circuit breaker is reset.