beautypg.com

P6sp charging charts, cooling only – Reznor P6SP Unit Installation Manual User Manual

Page 30

background image

30

180

200

220

240

260

280

300

320

340

360

380

400

420

440

460

480

500

520

540

560

580

50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135

Li

qui

d

Pr

es

sur

e

(ps

ig)

Liquid Temperature (F)

Charging Chart - Cooling Operation - 6T P6 Units

Add refrigerant when below curve

Remove refrigerant when above curve

P6sP cHarGInG cHarts, coolInG onlY

This equipments cooling systems contain refrigerant under

high pressure, always use safe practices when servicing

the unit. Always review the factory literature and safety

warnings prior to servicing.
All P6SP-072/090/120 units are shipped from the factory

with the proper amount and type of refrigerant. Always

inspect the unit rating label to determine the units

information prior to working on the system. Do not mix

different refrigerants or charge the unit with a refrigerant

not listed on the unit rating label.
The charging charts below are valid for a variety of indoor,

return air conditions and are most highly influenced by

the outdoor ambient temperature, outdoor fan operation

and the unit operating voltage. Before referencing the

charts below, always ensure that all compressor circuits

are energized and have stable operation. As can be seen

in the charging charts, the ideal system sub-cooling can

vary over the range of operation. Always reference the

charts to determine the ideal amount of sub-cooling for

a given liquid pressure. Units charged to other values will

not perform at the rated unit efficiency (EER).

To inspect a systems operation, using quality instruments,

aPPlIcatIon notEs on tHE usE oF cHarGInG cHarts

match the measured liquid temperature to the units chart.

The measured liquid pressure reading should be within

3% of the value shown for most installations. For two stage

systems, the charts are valid for both compressor stages.
DO NOT utilize the charts for two stage systems operating

only under a single stage call for cooling.
DO NOT utilize the charts in systems that do not have

all the outdoor fans energized, or have the fans cycling

under a low-ambient control. Refer to the low-ambient kit

instructions for more information, if applicable.
For systems that are operating with more then a 5%

deviation, inspect the unit for leaks. Always use safe and

environmentally sound methods for refrigerant handling.

When repairing system leakages, always utilize a nitrogen

(inert) gas to protect the refrigerant system and pressure

check the repair before re-charging. Always replace the

filter-dryers when performing any repair to the refrigeration

system. After completing the repairs, evacuate the system

to 350-500 microns and weight in the refrigerant to the

amount specified on the unit rating label.

Figure 15. charging chart for single stage cooling systems - 6 ton units