beautypg.com

P6sp-072(c/d) – Reznor P6SP Unit Installation Manual User Manual

Page 25

background image

25

P6sP-072(c/D)

Factory Standard: 1.5Hp Horizontal Performance Chart

‡ Indicates Factory Sheave Setting for Pre-configured Units

External

Unit

Static

(in-Wg)

Operating

@ 230 or

460 Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2

Turn

Open

1

Turn

Open

1.5

Turns

Open ‡

2.0

Turns
Open

2.5

Turns
Open

3.0

Turns
Open

3.5

Turns
Open

4.0

Turns
Open

4.5

Turns
Open

5.0

Turns
Open

5.5

Turns
Open

6.0

Turns
Open

0.2

CFM

2665

RPM

727

kW

0.74

0.3

CFM

2720

2584

2447

RPM

781

755

729

kW

0.82

0.75

0.67

0.4

CFM

2654

2504

2346

2188

RPM

808

784

757

730

kW

0.85

0.74

0.67

0.60

0.5

CFM

2591

2425

2258

2081

1904

RPM

836

812

788

760

731

kW

0.88

0.77

0.67

0.60

0.54

0.6

CFM

2687

2518

2349

2177

2005

RPM

885

862

838

815

791

kW

0.98

0.88

0.79

0.69

0.59

0.7

CFM

2460

2276

2092

RPM

889

865

841

kW

0.90

0.80

0.70

0.8

CFM

2572

2383

2193

2007

1821

RPM

937

915

892

869

846

kW

1.04

0.93

0.82

0.73

0.63

0.9

CFM

2325

2137

1948

RPM

940

919

898

kW

0.93

0.82

0.72

1.0

CFM
RPM

kW

Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil
When utilized with H5HK Heater kits, not all operational points shown may be available for use. Refer to the H5HK Installation
Instructions to determine the minimum airflow requirements of the applicable heater assembly.
Deduct 250 Cfm for electric heater kits

table 6. Blower Performance for P6sP-072(c,D) series

(6 ton Horizontal Models only)