C-PRO GIGA HARDWARE MANUAL

Pag. 40

7

Configuration of the supplied analogic outputs
signal


C-PRO GIGA has four analogic outputs.
Each analogic output can be configured to supply one of the following signal :

0,5-10 V (called voltage)

0-20 mA (called current)

4-20 mA (called current).


To configurate the signal supplied by the analogic output it is necessary :

positioning the appropriate JMP6 jumper in the selected position (see chapter 2.2 “C-PRO

GIGA wiring layout on page 17, jumper and LED meaning ; the configuration jumper is
JMP6)

confirming the choice selected with the “controller’s parameters” relative to the analogic

outputs as shown on the following paragraph .

7.1

Parameters configuration relative to the analog output


By logging on the controller parameters’ configuration procedure relative to the analogic outputs
act in the following way :

Both for the remote or built-in user interface :

1.

Ensure that the controller and the user interface are both switched on and no utilization is

connected to the analogic outputs .

2.

Keep both

and

buttons pressed together for two seconds : first available voice

will be visualized.

3.

Press and release

button to select “Parameters”.

4.

Press and release

button : “Input Password” will be visualized.

5.

Press and release

button: the cursor blinks.

6.

Press and release

button to set “ -19”.

7.

Press and release

button :first available voice will be visualized.

8.

Press and release

button :further available voice will be visualized.

9.

Press and release

button to select one of the voice “Type AO1 … AO4”.

10.

Press and release

button : the cursor blinks.