C-PRO GIGA HARDWARE MANUAL
Pag. 40
7
Configuration of the supplied analogic outputs
signal
C-PRO GIGA has four analogic outputs.
Each analogic output can be configured to supply one of the following signal :
•
0,5-10 V (called voltage)
•
0-20 mA (called current)
•
4-20 mA (called current).
To configurate the signal supplied by the analogic output it is necessary :
•
positioning the appropriate JMP6 jumper in the selected position (see chapter 2.2 “C-PRO
GIGA wiring layout on page 17, jumper and LED meaning ; the configuration jumper is
JMP6)
•
confirming the choice selected with the “controller’s parameters” relative to the analogic
outputs as shown on the following paragraph .
7.1
Parameters configuration relative to the analog output
By logging on the controller parameters’ configuration procedure relative to the analogic outputs
act in the following way :
Both for the remote or built-in user interface :
1.
Ensure that the controller and the user interface are both switched on and no utilization is
connected to the analogic outputs .
2.
Keep both
and
buttons pressed together for two seconds : first available voice
will be visualized.
3.
Press and release
button to select “Parameters”.
4.
Press and release
button : “Input Password” will be visualized.
5.
Press and release
button: the cursor blinks.
6.
Press and release
button to set “ -19”.
7.
Press and release
button :first available voice will be visualized.
8.
Press and release
button :further available voice will be visualized.
9.
Press and release
button to select one of the voice “Type AO1 … AO4”.
10.
Press and release
button : the cursor blinks.