beautypg.com

EVCO EVD120 User Manual

Page 33

background image

Evco S.r.l.

ModBUS PRJ314AA06 v1.02

12

th

December 2006

page 5 of 8

Max range of linear input 2
(corresponding to 20 mA or 10 V)

$0633 R/W

Default

1000

Kind of saturation of linear input 2

$0634

R/W

0 = no saturation
1 = saturation on min and max

range of linear input 2

2 = saturation on 0, 1000
3 = saturation on 0, 10000

INFO

Firmware

ID

$FF08 R

Firmware

Variation/revision

$FF09 R



(2) Digital filter: 3 is the default value.

(3) Probe kind

Value Meaning

0 PTC

1 NTC

2 TC

J

3 TC

K

4 Reserved

5

Pt 100 3 wires

6

Pt 100 2 wires

7 Rerserved

8 Rerserved

9

Pt 1000 3 wires

10

Pt 1000 3 wires

11 4-20

mA

12 0-20

mA

13 2-10

V

14 0-10

V




PAY ATTENTION:

ALL THE ADDRESSES NOT MENTIONED EXPRESSLY IN THIS DOCUMENT MUST BE CONSIDERED

RESERVED. IF YOU DO NOT RESPECT THIS CONDITION, YOU COULD ALTER THE OPERATION OF

THE INSTRUMENT.