Description
Address
(zero
based)
Access
Notes
PARAMETERS
Meas. unit (0 = Celsius, 1 = Fahrenheit)
$0601
R/W
Modbus nodes address
$0610
R/W
Baud Rate
$0611
R/W
Parity $0612
R/W
Enable Auto-incremental address
$0613
R/W
Kind of digital input 1 (0 = NO, 1 = NC)
$061F
R/W
msk $0001 = digital In 1
msk $0002 = digital In 2
Probe 1 configuration
$0620
R/W
bit0 = Enable
bit1..3 = reserved
bit4..7 = Digital filter (2)
bit8..11 = probe kind (3)
bit12..15 = reserved
Probe 1 offset
$0621
R/W
Default 0
Min range of linear input 1
(corresponding to 0/4 mA or 0/2 V)
$0622 R/W
Default
0
Max range of linear input 1
(corresponding to 20 mA or 10 V)
$0623 R/W
Defailt
1000
Kind of saturation of linear input 1
$0624
R/W
0 = no saturation
1 = saturation on min and max
range of linear input 1
2 = saturation on 0, 1000
3 = saturation on 0, 10000
Probe 2 configuration
$0630
R/W
bit0 = Enable
bit1..3 = reserved
bit4..7 = Digital filter (2)
bit8..11 = probe kind (3)
bit12..15 = reserved
Probe 2 offset
$0631
R/W
Default 0
Min range of linear input 2
(corresponding to 0/4 mA or 0/2 V)
$0632 R/W
Default
0