Evd120, Technical data, 5technical data – EVCO EVD120 User Manual

Page 25

background image

25

EVD120

Technical data

5

Technical data

5.1

Technical data

Box:

self-extinguishing grey.

Frontal protection:

IP 40.

Connections:

screw terminal blocks (power supply, inputs and port for the serial communication)

6 poles connector (port for the communication with the programming key).

Working temperature:

from 0 to 55 °C (32 to 131 °F, 10 ... 90% of relative humidity without condensate).

Power supply:

230 VAC, 50/60 Hz, 1.5 VA (approximate).

Analog channels:

2 (analog channel 1 and analog channel 2) for:

PTC/NTC probes

J/K thermocouples

2/3 wires Pt 100 and Pt 1000 probes

2/3 wires 4-20 mA passive current transducers

0-10/2-10 V and 0-20/4-20 mA active transducers

(universal analog channels).

Digital inputs:

2 (digital input 1 and digital input 2) for NO/NC contact (free of voltage, 12 V 5 mA approximate).

Working range:

from -50 to 150 °C (-50 to 300 °F) for PTC probe

from -40 to 110 °C (-40 to 230 °F) for NTC probe

from -100 to 800 °C (-140 to 1,450 °F) for J thermocouple

from -100 to 1,300 °C (-140 to 2,350 °F) for K thermocouple

from -100 to 650 °C (-140 to 1,200 °F) for 2/3 wires Pt 100 probe

from -100 to 650 °C (-140 to 1,200 °F) for 2/3 wires Pt 1000 probe.

Resolution:

0.1 for 2/3 wires 4-20 mA passive current transducers and for 0-10/2-10 V and 0-20/4-20 mA active transducers

0.1 °C/1 °F otherwise.

Serial ports:

port for the serial communication (via RS-485, with MODBUS communication protocol)

port for the communication with the programming key.

[ EVD120 ]

Technical data