Evd120, Configuration parameters, 3configuration parameters – EVCO EVD120 User Manual
Page 19
19
EVD120
Configuration parameters
3
Configuration parameters
3.1
Preliminary remarks
Configuration parameters are visible using one of the following software:
•
RICS
•
Params Manager.
3.2
Configuration parameters
TEXT FIELD
MIN.
MAX. U.M.
DEF.
ANALOG CHANNELS
Celsius Fahrenheit
0
1
- - -
0
unit of measure temperature
(11)
0 =
°C
1 =
°F
Enable Probe 1
0
1
- - -
1
enabling the analog channel 1
1 =
YES
Enable Probe 2
0
1
- - -
1
enabling the analog channel 2
1 =
YES
Probe kind 1
0
14
- - -
1
kind of probe analog channel 1
(12)
0 =
PTC
1 =
NTC
2 =
J
3 =
K
4 =
reserved
5 =
3 wires Pt 100
6 =
2 wires Pt 100
7 =
reserved
8 =
reserved
9 =
3 wires Pt 1000
10 =
2 wires Pt 1000
11 =
4-20 mA
12 =
0-20 mA
13 =
2-10 V
14 =
0-10 V
Probe kind 2
0
14
- - -
1
kind of probe analog channel 2
(12)
0 =
PTC
1 =
NTC
2 =
J
3 =
K
4 =
reserved
5 =
3 wires Pt 100
6 =
2 wires Pt 100
7 =
reserved
8 =
reserved
9 =
3 wires Pt 1000
[ EVD120 ]
Configuration parameters
(11) if parameters “Probe kind 1”
and/or “Probe kind 2” have value 8,
9, 10 or 11, parameter “Celsius Fahr-
enheit” will have no effect
(12) switch off/on the power sup-
ply of the instrument after the modi-
fication of the parameter