EVCO EVD120 User Manual
Page 20
20
EVD120
Configuration parameters
10 =
2 wires Pt 1000
11 =
4-20 mA
12 =
0-20 mA
13 =
2-10 V
14 =
0-10 V
Probe1 Offset
-25.0
25.0
(13)
0.0
offset analog channel 1
Probe2 Offset
-25.0
25.0
(13)
0.0
offset analog channel 2
DigitalFilter probe 1
0
6
- - -
3
reading speed analog channel 1 (0 = fast ... 6 = slow)
(12)
DigitalFilter probe 2
0
6
- - -
3
reading speed analog channel 2 (0 = fast ... 6 = slow)
(12)
MinTarI 1
-1500.0 1500.0 points 0.0
minimum value of the range of the transducer of the ana-
log channel 1 corresponding to 0/4 mA or 0/2 V
MinTarI 2
-1500.0 1500.0 points 0.0
minimum value of the range of the transducer of the ana-
log channel 2 corresponding to 0/4 mA or 0/2 V
MaxTarI 1
-1500.0 1500.0 points 100.0
maximum value of the range of the transducer of the ana-
log channel 1 corresponding to 20 mA or 10 V
MaxTarI 2
-1500.0 1500.0 points 100.0
maximum value of the range of the transducer of the ana-
log channel 2 corresponding to 20 mA or 10 V
Saturation
0
3
- - -
0
values the signal of the transducer of the analog channel 1
Configuration 1
saturates (or finishes being converted by the instrument)
0 =
function not enabled
1 =
below “MinTarI 1” and above “MaxTarI 1”
2 =
below 0.0 and above 100.0
3 =
below 0.0 and above 1000.0
Saturation
0
3
- - -
0
values the signal of the transducer of the analog channel 2
Configuration 2
saturates (or finishes being converted by the instrument)
0 =
function not enabled
1 =
below “MinTarI 2” and above “MaxTarI 2”
2 =
below 0.0 and above 100.0
3 =
below 0.0 and above 1000.0
TEXT FIELD
MIN.
MAX. U.M.
DEF.
DIGITAL INPUTS
Polarity Digital Input 1
0
1
- - -
0
kind of contact digital input 1
0 =
NO (input active if you close the contact)
1 =
NC (input active if you open the contact)
Polarity Digital Input 2
0
1
- - -
0
kind of contact digital input 2
0 =
NO (input active if you close the contact)
1 =
NC (input active if you open the contact)
TEXT FIELD
MIN.
MAX. U.M.
DEF.
SERIAL COMMUNICATION (MODBUS)
Address
1
247
- - -
247
instrument address
(12)
Baud rate
0
3
- - -
2
baud rate
(12)
0 =
2,400 baud
1 =
4,800 baud
2 =
9,600 baud
3 =
19,200 baud
Parity
0
2
- - -
2
parity
(12)
0 =
none
1 =
odd
2 =
even
(13) the unit of measure depends on
parameters “Celsius Fahrenheit” (°C
or °F) and “Probe kind 1” or “Probe
kind 2” (temperature or variable of
the range of the transducer).