EVCO EVD120 User Manual

Page 20

background image

20

EVD120

Configuration parameters

10 =

2 wires Pt 1000

11 =

4-20 mA

12 =

0-20 mA

13 =

2-10 V

14 =

0-10 V

Probe1 Offset

-25.0

25.0

(13)

0.0

offset analog channel 1

Probe2 Offset

-25.0

25.0

(13)

0.0

offset analog channel 2

DigitalFilter probe 1

0

6

- - -

3

reading speed analog channel 1 (0 = fast ... 6 = slow)

(12)

DigitalFilter probe 2

0

6

- - -

3

reading speed analog channel 2 (0 = fast ... 6 = slow)

(12)

MinTarI 1

-1500.0 1500.0 points 0.0

minimum value of the range of the transducer of the ana-

log channel 1 corresponding to 0/4 mA or 0/2 V

MinTarI 2

-1500.0 1500.0 points 0.0

minimum value of the range of the transducer of the ana-

log channel 2 corresponding to 0/4 mA or 0/2 V

MaxTarI 1

-1500.0 1500.0 points 100.0

maximum value of the range of the transducer of the ana-

log channel 1 corresponding to 20 mA or 10 V

MaxTarI 2

-1500.0 1500.0 points 100.0

maximum value of the range of the transducer of the ana-

log channel 2 corresponding to 20 mA or 10 V

Saturation

0

3

- - -

0

values the signal of the transducer of the analog channel 1

Configuration 1

saturates (or finishes being converted by the instrument)

0 =

function not enabled

1 =

below “MinTarI 1” and above “MaxTarI 1”

2 =

below 0.0 and above 100.0

3 =

below 0.0 and above 1000.0

Saturation

0

3

- - -

0

values the signal of the transducer of the analog channel 2

Configuration 2

saturates (or finishes being converted by the instrument)

0 =

function not enabled

1 =

below “MinTarI 2” and above “MaxTarI 2”

2 =

below 0.0 and above 100.0

3 =

below 0.0 and above 1000.0

TEXT FIELD

MIN.

MAX. U.M.

DEF.

DIGITAL INPUTS

Polarity Digital Input 1

0

1

- - -

0

kind of contact digital input 1

0 =

NO (input active if you close the contact)

1 =

NC (input active if you open the contact)

Polarity Digital Input 2

0

1

- - -

0

kind of contact digital input 2

0 =

NO (input active if you close the contact)

1 =

NC (input active if you open the contact)

TEXT FIELD

MIN.

MAX. U.M.

DEF.

SERIAL COMMUNICATION (MODBUS)

Address

1

247

- - -

247

instrument address

(12)

Baud rate

0

3

- - -

2

baud rate

(12)

0 =

2,400 baud

1 =

4,800 baud

2 =

9,600 baud

3 =

19,200 baud

Parity

0

2

- - -

2

parity

(12)

0 =

none

1 =

odd

2 =

even

(13) the unit of measure depends on

parameters “Celsius Fahrenheit” (°C

or °F) and “Probe kind 1” or “Probe

kind 2” (temperature or variable of

the range of the transducer).