Kc-h-app-d -29-10, Water heater default settings, Appendix d – AERCO KC Series Equipped with C-More version 3.04 User Manual

Page 89

background image

APPENDIX D

D-1

WATER HEATER DEFAULT SETTINGS

MENU & OPTION

FACTORY DEFAULT

Setup Menu

Password

0

Language

English

Unit of Temp

Fahrenheit

Comm Address

0

Baud Rate

9600

Configuration Menu

Internal Setpt

130°F

Unit Type

KC Water Heater

Fuel Type

Natural Gas

Unit Size

1.0 MBTU

Heater Mode

Constant Setpoint

Remote Signal
(If Heater Mode = Remote Setpoint)

4 – 20 mA ,/ 1-5V

Outdoor Sensor

Disabled

Setpt Lo Limit

60°F

Setpt Hi Limit

200°F

Temp Hi Limit

210°F

Max Valve Position

100%

Aux Start On Dly

0 sec

Failsafe Mode

Shutdown

mA Output

Off

Lo Fire Timer

2 sec.

Setpt Limiting

Disabled

Setpt Limit Band

5°F

Network Timeout

30 seconds

HI DB Setpt En

30

Demand Offset

10

Deadband High

2

Deadband Low

2