beautypg.com

Installation – AERCO KC Series Equipped with C-More version 3.04 User Manual

Page 17

background image

INSTALLATION

2-7

2.6.1 OUTDOOR AIR SENSOR IN

Not applicable to Water Heaters.

2.6.2 AUX SENSOR IN

The AUX SENSOR IN terminals can be used to

add an additional temperature sensor for

monitoring purposes. This input is always

enabled and is a view only input that can be

seen in the operating menu. The sensor must be

wired to the AUX SENSOR IN and SENSOR

COMMON and must be similar to AERCO

BALCO wire sensor P/N 12449. A resistance

chart for this sensor can be found in Appendix C.

2.6.3 ANALOG IN

The ANALOG IN + and – terminals are used

when an external signal is used to change the

setpoint of the water heater when operating in

the Remote Setpoint Mode.

Either a 4 to 20 mA / 1 to 5 VDC or a 0 to 20 mA/

0 to 5 VDC signal may be used to vary the

setpoint or air/fuel valve position. The factory

default setting is for 4 to 20 mA / 1 to 5 VDC,

however this may be changed to 0 to 20 mA / 0

to 5 VDC using the Configuration Menu

described in Section 3. If voltage rather than

current is selected as the drive signal, a DIP

switch must be set on the CPU Board located

inside the Control Box. Contact the AERCO

factory for information on setting DIP switches.

All supplied signals must be floating

(ungrounded) signals. Connections between the

source and the Heater’s I/O Box must be made

using twisted shielded pair wire of 18 –22

AWG,,such as Belden 9841(see Fig. 2.10).

Polarity must be maintained and the shield must

be connected only at the source end. It must be

left floating (not connected) at the Heater’s I/O

Box.

Whether using voltage or current for the drive

signal, they are linearly mapped to a 40°F to

240°F setpoint or a 0% to 100% valve position.

No scaling for these signals is provided

2.6.4 B.M.S. (PWM) IN

Not applicable to Water Heaters.

2.6.5 SHIELD

The SHIELD terminals are used to terminate any

shields used on sensor wires connected to the

unit. Shields must only be connected to these

terminals.

2.6.6 mA OUT

These terminals provide a 4 to 20 mA output that

can be used to monitor setpoint ( to 220°F),

outlet temperature (

to 245°F), or valve position

(0% to 100%). This function is enabled in the

Configuration Menu (Section 3, Table 3.4).

2.6.7 RS-485 COMM

These terminals are used for RS-485 MODBUS

serial communication between the unit and an

external “Master”, such as an Energy Manage-

ment System.

2.6.8 EXHAUST SWITCH IN

These terminals permit an external exhaust

switch to be connected to the exhaust manifold

of the boiler. The exhaust sensor should be a

normally open type switch (such as AERCO P/N

123463) that closes (trips) at 500°F.

2.6.9 INTERLOCKS

The unit offers two interlock circuits for

interfacing with Energy Management Systems

and auxiliary equipment such as pumps or

louvers or other accessories. These interlocks

are called the Remote Interlock and Delayed

Interlock (Fig. 2.10). The wiring terminals for

these interlocks are located inside the I/O Box

on the left side of the unit. The I/O Box cover

contains a wiring diagram which shows the

terminal strip locations for these interlocks

labeled REMOTE INTL’K IN and DELAYED

INTL’K IN. Both interlocks, described below, are

factory wired in the closed position.

NOTE:

Both the Delayed Interlock and Remote

Interlock must be in the closed position to

allow the unit to fire.

2.6.9.1 REMOTE INTERLOCK IN

The remote interlock circuit (REMOTE INTL’K

IN) is provided to remotely start (enable) and

stop (disable) the unit if desired. The circuit is

24 VAC and comes factory pre-wired closed

(jumped).

2.6.9.2 DELAYED INTERLOCK

The delayed interlock circuit (DELAYED INTL’K

IN) is typically used in conjunction with the

auxiliary relay described in paragraph 2.6.11.

This interlock circuit is located in the purge

section of the start string. It can be connected to

the proving device (end switch, flow switch etc.)

of an auxiliary piece of equipment started by the

unit’s auxiliary relay. The delayed interlock must

be closed for the heater to fire. If the delayed

interlock is connected to a proving device that