beautypg.com

10 fault relay, Figure 2.10 i/o box wiring, 7 flue gas vent installation – AERCO KC Series Equipped with C-More version 3.04 User Manual

Page 18: Installation, Danger

background image

INSTALLATION

2-8

requires time to close (make), a time delay (Aux

Start On Dly) that holds the start sequence of the

unit long enough for a proving switch to make

(close) can be programmed. Should the proving

switch not prove within the programmed time

frame, the unit will shut down. The Aux Start On

Dly can be programmed from 0 to 120 seconds.

This option is locate in the Configuration Menu

(Section 3).

2.6.10 FAULT RELAY

The fault relay is a single pole double throw

(SPDT) relay having a normally open and

normally closed set of relay contacts that are

rated for 5 amps at 120 VAC and 5 amps at 30

VDC. The relay energizes when any fault

condition occurs and remains energized until the

fault is cleared and the

CLEAR button is

depressed. The fault relay connections are

shown in Figure 2.10.

2.6.11 AUXILIARY RELAY CONTACTS

Each unit is equipped with a single pole double

throw (SPDT) relay that is energized when there

is a demand for heat and de-energized after the

demand for heat is satisfied. The relay is

provided for the control of auxiliary equipment,

such as pumps and louvers, or can be used as a

unit status indictor (firing or not firing). Its

contacts are rated for 120 VAC @ 5 amps.

Refer to Figure 2.10 to locate the AUX RELAY

terminals for wiring connections.

mA OUT

RS-485

COMM.

+

-

+

-

ANALOG IN

SENSOR COMMON

OUTDOOR SENSOR IN

REMOTE INTL'K IN

B.M.S. (PWM) IN

SHIELD

+

-

+

-

AUX SENSOR IN

NOT USED

EXHAUST SWITCH IN

DELAYED INTL'K IN

FAULT RELAY

120 VAC, 5A, RES

AUX RELAY

120 VAC, 5A, RES

G

RELAY CONTACTS:

120 VAC, 30 VDC

5 AMPS RESISTIVE

DANGER

120 VAC USED

IN THIS BOX

NOT USED

NOT USED

NC

COM

NO
NC

COM

NO

NOT USED

Figure 2.10 I/O Box Wiring

2.7 FLUE GAS VENT INSTALLATION

AERCO Gas Fired Venting and Combustion Air

Guide, GF-1050, must be consulted before any

flue or combustion air venting is designed or

installed. Suitable, U/L approved, positive

pressure, watertight vent materials MUST be

used for safety and UL certification. Because

the unit is capable of discharging low

temperature exhaust gases, the flue must be

pitched back towards the unit a minimum of 1/4"

per foot to avoid any condensate pooling and to

allow for proper drainage.

While there is a positive flue pressure during

operation, the combined pressure drop of vent

and combustion air systems must not exceed

140 equivalent feet of 0.81” W.C. Fittings as

well as pipe lengths must be calculated as part

of the equivalent length. For a natural draft

installation the draft must not exceed - 0.25”

W.C. These factors must be planned into the

vent installation. If the maximum allowable

equivalent lengths of piping are exceeded, the

unit will not operate properly or reliably.