INITIAL START-UP

4-9

3. Once stabilized, the

OUTLET TEMPERATURE display should read no more than 2 to 3 degrees

above the unit’s setpoint.

4. If the outlet temperature is stabilized, proceed to the Maximum Load Adjustment procedure in

paragraph 4.6.3. If the unit is not stabilized, proceed to step 5.

5. Press the

MENU key and select the Tuning Menu.

6. Press the ▲ or ▼ arrow key until Min Load Adj is displayed.

7. Press the

CHANGE key. The display will begin to flash.

8. Raise or lower the minimum load adjustment in increments of one or two using the ▲ or ▼ arrow key.

Increasing this value will increase the outlet water temperature, while decreasing it will decrease the

water temperature.

9. Press

ENTER to save the change. Allow time for the system to stabilize between adjustments

10. Repeat steps 5 through 9 as needed until the temperature is stabilized at no more than 2 to 3 degrees

above the setpoint.

4.6.3 MAXIMUM LOAD ADJUSTMENT

Check the temperature control at minimum load as follows:

1. While monitoring the

VALVE POSITION display, create a maximum load on the system that will yield

a steady valve position between 80% and 90%.

NOTE:

It may be necessary to open the outlet valve if it was closed during minimum load adjustment to obtain a

sufficient flow rate for maximum adjustment.

2. Wait several minutes to allow the outlet temperature to stabilize under load conditions.

3. Once the temperature has stabilized, the

OUTLET TEMPERATURE display should read no more

than 2 to 3 degrees below the unit’s setpoint.

4. If the outlet temperature is stabilized, no adjustment is necessary. If the unit is not stabilized, proceed

to step 5.

5. Press the

MENU key and select the Tuning Menu.

6. Press the ▲ or ▼ arrow key until Max Load Adj is displayed.

7. Press the

CHANGE key. The display will begin to flash.

8. Raise or lower the maximum load adjustment using the ▲ or ▼ arrow key. Increasing this value will

increase outlet water temperature, while decreasing it will decrease water temperature.

9. Press

ENTER to save the change. Allow time for the system to stabilize between adjustments

10. Repeat steps 5 through 9 as needed until the temperature is stabilized 2 to 3 degrees below the

setpoint.

11. If the outlet temperature does not maintain setpoint after a reasonable amount of time and adjustment,

contact your local AERCO representative.

NOTE:

After performing Temperature Calibration and prior to placing the water heater in service, be sure to turn

the Outlet Feedback option in the Tuning Menu back to ON.