beautypg.com

Figure 3.1, Front panel controls location, Control panel operating procedures – AERCO KC1000 Boiler equipped with Mod-Box Controller User Manual

Page 15

background image

CONTROL PANEL OPERATING PROCEDURES

10

SECTION 3- CONTROL PANEL OPERATING PROCEDURES

The following is a guide to the operation of the
control panel. Initial start-up of this unit must be
performed by factory trained start-up personnel.
Operation prior to initial start-up by factory
trained personnel will void the warranty.

CAUTION:

All initial installation procedures must be

satisfied before attempting to start the unit.

WARNING:

DO NOT ATTEMPT TO DRY FIRE THE KC

1000. STARTING THE UNIT WITHOUT A

FULL WATER LEVEL CAN SERIOUSLY

DAMAGE THE UNIT AND MAY RESULT IN

PERSONNEL INJURY OR PROPERTY

DAMAGE. THIS SITUATION WILL VOID

ANY WARRANTY.

3.1 THE CONTROL PANEL

The KC 1000 Control Panel has been designed
to provide the operator with all the necessary
information required for operating and
troubleshooting this unit. There are six separate
accessible controls or displays, available to the
operator, (see Fig. 3.1). These are:

1. The Temperature Controller
2. The Annunciator & Function Switches
3. The Combustion Safeguard Controller
4. Water Level Test and Reset Switches
5. On/Off

Switch

6. Fault Indicator Light

The following sections will describe the above
components in more detail.

WARNING

CONTROL BOX INTERNALS MUST NOT

BE SERVICED OR ACCESSED BY

OTHER THAN FACTORY CERTIFIED

SERVICE TECHNICIANS. ALL CONTROL

BOX INTERNALS HAVE THE CAPABILITY
OF HOLDING AN ELECTRICAL VOLTAGE

OF 120 VOLTS AC.

3.2 THE TEMPERATURE CONTROLLER

The temperature controller is a PID
programmable controller that utilizes feed
forward and feedback information to accurately
maintain a desired set point. It is the primary
source for programming and viewing operating
parameter settings. It plays a part in the start
sequence and includes other features such as:

2- eight segment LED displays

5 indicator status lights

3 menu levels

RS-485 communications capability

Figure 3.1

Front Panel Controls Location

3.2.1 LED DISPLAYS

The upper and lower displays each consists of
four, 8 segment LED’s (see Fig. 3.2). When
choosing an operating parameter to be changed
or looked at, the lower LED display indicates the
parameter being looked at in the form of a code.
The upper display indicates the parameter’s
value. For a complete listing of the operating
parameters, see Appendix A of this manual.

3.2.2 INDICATOR STATUS LIGHTS

The first LED indicator light, “MAN” indicates
whether the controller is in auto or manual
mode, (see Fig 3.2). When lit the controller is in
manual mode and the operator is responsible for
operation of the unit. When the LED is not lit the
controller is in auto mode. In auto mode the
controller is operating the unit from signals
generated by sensors located on the unit or in
the system, or by signals from an energy
management system.

The second LED, “REM”, designates whether
the controller is being controlled locally or
remotely, (see Fig. 3.2). When lit the controller is
in remote mode and can accept commands from
an external source via the RS-485 interface.
When this LED is not lit the controller is in local
mode and will respond to whatever the current
internal settings are. All external commands are
ignored.