3-2 I/O Communication
3-16
- DeviceNet Compatible Network Unit DL-DN1 User’s Manual (SK-1000) -
3
Comm
u
nic
a
ti
ng
w
it
h th
e
SK-1
000 Se
ri
es
Entering an external input into a sensor amplifier
Available external inputs: External inputs 1 - 4
Device assignments:
This example illustrates how to enter a TIMING input into the sensor amplifier of ID01.
It assumes that the operating mode assigned to the device is 3-output mode.
(1) The device value in the OUT area which is assigned an external input request is
linked via I/O communication, so that the external input of the sensor amplifier is
turned on or off.
(2) The input status of the sensor amplifier can be checked with the external input
response.
• An "amplifier unit external input ON" status is recognized when
either the "external input from communication" or the "amplifier
unit input signal line" is ON, and input operation is executed (OR
operation).
[Example] Suppose that the external input n is set to "reset input."
The reset input is executed if the external input via
communication or the input signal line of the sensor
amplifier is ON.
• When bank switching is used, the amplifier unit's "BANK switching
method" must be specified as "external input switching".
PLC
(1)
External Input request
OUTarea [m+1]Bit0
(2)
External Input response
IN area [n+5]Bit0
Sensor amplifier
External Input
External input 2 for ID 01
1
0
ON
OFF
1
0
Point