Hardy HI 2151/30WC Single-Scale Controller User Manual
Page 61
Section 8: Troubleshooting
55
32
8
Reserved for future use
33
12
1
81
51
Tare value exceeds legal range
of -99,999-999,999
34
2
82
52
Units of measure are
0=Pounds/1=Kilograms
35
3
Reserved for future use
36
4
85
54
Totalizer decimal point must be
equal or less than decimal point
position (0-4)
37
5
85
55
C2 load cell count must be
between 0-8
38
6
86
56
Sticker value must be a 6 digit
number (between 65536-
999999)
39
7
87
57
Analog out should be -99,999
and 999,999
40
8
88
58
Analog low count can’t equal
high count
41
13
1
89
59
Scale in Calibration Mode*
42
2
101
Invalid WAVERSAVER
43
3
Reserved for future use
44
4
96
60
Load cell count error
45
5
97
61
No C2
®
load cells found
46
6
98
62
Load cell capacity/sensitivity
error
47
7
99
63
Load cell checksum error
48
8
100
64
Too many significant digits after
the decimal to be displayed
TABLE 8-1 RESPONSE/ERROR CODES
NOTES:
Writes are not allowed while scale is in calibration mode.
The first 6 bytes of the diagnostic information is reserved as defined in the Profibus
Standard. Bytes 7-13 are used by the HI 2151 Series -B12 PROFIBUS interface option to
provide automatic response/error codes.
8.4
CLEARING PROFIBUS DIAGNOSTIC CODE ASSOCIATED BIT(S)
1. A separate bit is reserved for each response/error code. When a response/error occurs, an
associated bit will be set to 1. This bit will remain set to 1 until it is cleared.
2. Clearing the error/code associated bit procedures.
a. Operator Selectable Transfer, rerun the Write “0" command.
b. Block Transfer, request the Read Block #90 via a Block Write 24 with data 90.