Section 6: Selectable Reads
43
6.7.10 INSTRUMENT ID
6.7.11 INSTRUMENT IDENTIFICATION
6.7.12 RESPONSE/ERROR CODE
Instrument ID
# Words
#
Bytes
Parameter
#
Hex
Number
Tare Weight
Net Weight
Gross Weight
Print Initiation (0 = Continuous, 1 = Altered
print)
Reserved for future use (must be set to 0)
Baud Rate (0 = 600, 1 = 1200, 2 = 2400,
3 = 4800, 4 = 9600, 5 = 19200)
Port Configuration (must be set to 1for printer
output only)
Stop Bits (0 = one stop bit, 1 = two stop bits)
Parity (0 = none, 1 = even, 2 = odd)
Handshake Control (0 = hardware, 1 = software)
Word Length (0 = seven bits, 1 = eight bits)
Device Address (a value from 0-99)
Echo (0 = off, 1 = on)
bit 3
bit 4
bit 5
bit 6
bit 7
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
1
1
1
1
1
1
1
1
91
92
93
94
95
96
97
98
5B
5C
5D
5E
5F
60
61
62
Instrument Identification
#
Words
#
Bytes
Parameter
#
Hex
Number
Firmware Revision Level (one character text, i.e. A)
(Pursuant to Revision Specification ASME
Y14.35M-1992)
Firmware Version (ASCII text number)
Zero Calibration analog-to-digital converter raw
counts
Span Calibration analog to digital converter raw
counts
0.5
2
2
2
1
4
4
4
100
101
102
103
64
65
66
67
Response/Error Code
#
Words
#
Bytes
Parameter
#
Hex
Number
Provide the last write command number with its
response/error code. (See Chapter 8 for a list of
response/error codes)
1
2
0
0