Page 77: Chapter 5: alarm programming 74

background image

5.4 Establishing High and Low Temperature Limits

High and low temperature limits can be separately programmed
for each zone configured as temperature. Limits can range from
–20° to +150° Fahrenheit, or from –30° to 65° Celsius.

When temperature limits exceed high or low settings, the Model
400 will dial out with an alarm message. Default settings are: 10°
F for low temperature and 100° F for high temperature.

5.4.1 Programming Temperature Limits for a Selected

Zone

1. Press SET.

SET

2. Press TEMP LIMITS.

5

TEMP LIMITS

3. From the number keys, press a number (from 1 to 4) that
corresponds to the temperature zone being programmed.

4

MAX CALLS

5

TEMP LIMITS

6

CALIBRATE

8

CLOCK

3

INTERCALL

TIME

7

RECOGNITION

TIME

9

LISTEN TIME

SOUND

0

ID NUMBER

POWER

1

CALL

DELAY

2

VOICE

REPS

The Model 400 responds: “Enter low temperature limit.”

4. Using the number keys, enter a value for low temperature
limit. The Model 400 will recite the digits as they are pressed. If a
negative number is required, first press *, then enter the number.

4

MAX CALLS

5

TEMP LIMITS

6

CALIBRATE

8

CLOCK

3

INTERCALL

TIME

7

RECOGNITION

TIME

9

LISTEN TIME

SOUND

0

ID NUMBER

POWER

1

CALL

DELAY

2

VOICE

REPS

Chapter 5: Alarm Programming

74