Problem cause solution, Other monitoring – Vintage Cellars FGD-0400 User Manual

Page 124

background image

Sensaphone

®

Model 400 User’s Manual

121

Problem

Cause

Solution

1.

Alarm

status

of

an

alert

zone

is

incorrect.

2.

False

power

out

alarms

3.

The

Model

400

does

not

recognize

power

failure.

Incorrect

zone

normality.

Programmed

Recognition

Time

is

too

short.

a)

Batteries

are

either

incorrectly

installed

or

drained.

b)

Recognition

time

setting

is

too

long.

Reconfigure

the

zone.

Refer

to

Chapter

5,

Section

5.1.

AC

power

is

often

subject

to

brief

interruptions.

To

avoid

frequent,

false

alarms,

increase

the

power

Recognition

Time.

Refer

to

Chapter

5,

Section

5.9.

To

verify

proper

battery

function,

unplug

the

unit

and

verify

continued

operation

using

bat

-

teries

only.

If

unit

ceases

to

function,

first

try

reinstalling

the

batteries.

If

this

is

not

suc

-

cessful,

replace

the

batteries.

Refer

to

Chapter

2,

Section

2.4

for

complete

instructions.

Reprogram

Recognition

Time.

Set

the

Recognition

Time

to

the

minimum

required

before

a

valid

alarm

occurs.

If

possible,

test

the

condition

by

deliberately

creating

an

alert

condition.

Refer

to

Chapter

5,

Section

5.9.

Other

Monitoring: