Configuring Alert Dial-Out
Set a few parameters to configure alert dial-out. The dial string and
alert string are set to send a message to a remote operator. When an
alert condition is triggered, the dial string is sent first, followed by the
alert string. Once the two strings are set, alert dial-out is enabled and
the new parameters should be verified. The elements of the dial string
and alert string are shown in Table 8–3.
You must configure remote dial-in for the dial-out feature to be enabled.
To set up the dial-out alert feature, enter the SCM from the local console device.
Example 8–2 Alert Dial-Out Configuration
SCM_E0> set dial atdt915551212
SCM_E0> set alert ,,,,5085551234#;
SCM_E0> enable alert
Enabling alerts
SCM_E0> test alert
SCM_E0> show status
System Management Settings
RMC escape sequence
:
Local BAUD/flow control
:
57600 / soft
COM1 BAUD/flow control
:
57600 / hard
Modem BAUD/flow control
:
57600 / hard
COM1 Mode
:
Pass-through
OCP power switch
:
Off
OCP HALT
:
Deasserted
OCP secure
:
Non-Secure
Remote access
:
Enabled
Remote user
:
Not Connected
Alerts
Enabled
Modem password
:
wffirmware
Modem init string
:
ate0v0&c1s0=2
Modem dial string
:
atdt915551212
Modem alert string
:
,,,,5085551234#;
Alert pending
:
YES
Most recent alert
:
User initiated ... from CSB node e0
SCM_E0> clear alert
Pending alert cleared
SCM_E0>