LCD Operation
|
Table 11. Settings
Settings
Submenu
Setting Option
Available Settings
Default Setting
Cumulative
Reset Peak Watts
[No] [Yes]
If No, no action.
If Yes, the Peak Consumption Watts value is
cleared and the date and time stamp for this
statistic is set to the present date and time.
No
Reset Peak Headroom Watts
[No] [Yes]
If No, no action.
If Yes, the Peak Headroom Watts value is
cleared and the date and time stamp for this
statistic is set to the present date and time.
No
Reset Cumulative kWh
[No] [Yes]
If No, no action.
If Yes, the Cumulative Consumption kWh
value is cleared and the date and time stamp for
this statistic is set to the present date and time.
No
L1 Settings
L1 Over Current Warning Level [0.0A]...[48.0A] *
[0.0A]...[32.0A] **
[0.0A]...[16.0A] ***
An input current amperage (A) reading greater
than this value causes a warning to generate.
This warning indicates that the current A
reading has risen to an unacceptable level.
38.4A
25.6A
12.8A
L1 Over Current Alarm Level
[0.0A]...[48.0A] *
[0.0A]...[32.0A] **
[0.0A]...[16.0A] ***
An input current amperage (A) reading greater
than this value causes an over current alarm to
generate.
48.0A
32.0A
16.0A
L1 Low Current Warning Level
[0.0A]...[48.0A] *
[0.0A]...[32.0A] **
[0.0A]...[16.0A] ***
An input current amperage (A) reading less
than this value causes a warning to generate.
This warning indicates that the current A
reading is reduced to an unacceptable level.
0.0A
0.0A
0.0A
* DELLM0001, DELLM001A, DELLM0004, DELLM004A, DELLM0006
** DELLM0002, DELLM0005, DELLM0007
*** DELLM0003
NOTE:
For Delta models, L1 represents L1-L3 data, L2 represents L1-L2 data, and L3 represents L2-L3 data.