beautypg.com

Dell Metered PDU LCD User Manual

Page 45

background image

45

LCD Operation

|

Table 11. Settings

Settings
Submenu

Setting Option

Available Settings

Default Setting

Cumulative

Reset Peak Watts

[No] [Yes]

If No, no action.

If Yes, the Peak Consumption Watts value is
cleared and the date and time stamp for this
statistic is set to the present date and time.

No

Reset Peak Headroom Watts

[No] [Yes]

If No, no action.

If Yes, the Peak Headroom Watts value is
cleared and the date and time stamp for this
statistic is set to the present date and time.

No

Reset Cumulative kWh

[No] [Yes]

If No, no action.

If Yes, the Cumulative Consumption kWh
value is cleared and the date and time stamp for
this statistic is set to the present date and time.

No

L1 Settings

L1 Over Current Warning Level [0.0A]...[48.0A] *

[0.0A]...[32.0A] **

[0.0A]...[16.0A] ***

An input current amperage (A) reading greater
than this value causes a warning to generate.
This warning indicates that the current A
reading has risen to an unacceptable level.

38.4A

25.6A

12.8A

L1 Over Current Alarm Level

[0.0A]...[48.0A] *

[0.0A]...[32.0A] **

[0.0A]...[16.0A] ***

An input current amperage (A) reading greater
than this value causes an over current alarm to
generate.

48.0A

32.0A

16.0A

L1 Low Current Warning Level

[0.0A]...[48.0A] *

[0.0A]...[32.0A] **

[0.0A]...[16.0A] ***

An input current amperage (A) reading less
than this value causes a warning to generate.
This warning indicates that the current A
reading is reduced to an unacceptable level.

0.0A

0.0A

0.0A

* DELLM0001, DELLM001A, DELLM0004, DELLM004A, DELLM0006

** DELLM0002, DELLM0005, DELLM0007

*** DELLM0003

NOTE:

For Delta models, L1 represents L1-L3 data, L2 represents L1-L2 data, and L3 represents L2-L3 data.