Current command – Dell Metered PDU LCD User Manual
Page 57

57
Serial Interface Operation
|
current command
Use this command to retrieve the present current measurement for each rPDU phase line.
Usage
where:
[summary] = Present current measurement
[X|Y|Z]
rPDU phase lines:
X = Phase L1
Y = Phase L2
Z = Phase L3
Retrieve the present current measurement for each rPDU phase line (L1, L2, or L3)
rPDU>current
Example
rPDU>current
rPDU: RMS current for phase X: 0.1A.
rPDU: RMS current for phase Y: 0.2A.
rPDU: RMS current for phase Z: 0.1A.
Retrieve a summary of current measurements for each rPDU phase (L1, L2, or L3)
rPDU>current [summary]
Example
rPDU>current summary
X:0.1A,0.0A,0.0A,0.0A
Y:0.2A,0.0A,0.0A,0.0A
Z:0.3A,0.0A,0.0A,0.0A
NOTE:
The summary response shows the present current reading as the first value; the other three values (minimum,
maximum, and average) will always be reported as zero.
Retrieve a summary of current measurements for a specific rPDU phase (L1, L2, or L3)
rPDU>current [summary][X|Y|Z]
Example
rPDU>current summary X
X:0.1A,0.0A,0.0A,0.0A
Retrieve the present current measurement for a specific rPDU
phase (L1, L2, or L3)
(Three-phase rPDUs only)
rPDU>current [X|Y|Z]
Example
rPDU>current X
rPDU: RMS current for phase X: 0.1A.