beautypg.com

Temperature command, Ver command – Dell Metered PDU LCD User Manual

Page 63

background image

63

Serial Interface Operation

|

temperature command

Use this command to retrieve the present temperature reading from the environmental monitoring sensor.

Usage

rPDU>temperature

Retrieve the present temperature reading from the environmental monitoring sensor

rPDU>temperature

Example

rPDU>temperature
rPDU: Temperature: 37.0oC.

ver command

Use this command to retrieve selected equipment, software version, and ratings information for the rPDU.

Usage

rPDU>ver

Retrieve selected rPDU equipment, software version, and ratings information

rPDU>ver

Example

rPDU>ver
rPDU: Hw with <30>outlets <96> AMPs max <22000> watts max DELL DPI 00.01.0028
August 5, 2010 id model <09FG8> [(3 phases) ].

where:

= Total number of outlets, regardless of outlet type (see Table 15)

= Maximum current for the rPDU

= Maximum wattage rating for the rPDU

= Software version number

= Dell Part Number (see Table 15)

[(3 phases) ]

= For an rPDU with 3-phase output only, Delta or Wye configuration

Table 15. and Value Description

Values

Descriptions

Values

1X98J

PDU 208V 17.3KW 3PH 6C13 12C19 (DELLM0001)

18

7P35N

PDU 200V 17.3KW 3PH 6C13 12C19 (DELLM001A)

18

09FG8

PDU 415V 22KW 3PH 18C13 12C19 (DELLM0002)

30

4J1C2

PDU 415V 11KW 3PH 21C13 6C19 (DELLM0003)

27

XX5T6

PDU 208V 17.3KW 3PH 42C13 (DELLM0004)

42

RXKCH

PDU 200V 17.3KW 3PH 42C13 (DELLM004A)

42

K5YYY

PDU 415V 22KW 3PH 42C13 (DELLM0005)

42

2CM2K

PDU 208V 17.3KW 3PH 48C13 (DELLM0006)

48

C0G4D

PDU 415V 22KW 3PH 48C13 (DELLM0007)

48