Measured and calculated meters – Dell Metered PDU LCD User Manual
Page 38
38
|
LCD Operation
Table 8. Performance Menu Selections (Fortsetzung)
Option
Description
Performance
Submenu
Power
Active Power
Provides the calculated value of the overall input,
displayed in watts (W)
Apparent Power
Provides the calculated value of the overall input,
displayed in Volt-amperes (VA)
Instantaneous Headroom Watts
Provides the watts capacity remaining
NOTE:
When the rPDU is in an overload state, this value
is always 0.
Peak Headroom Watts
Provides the remaining watts available to support the
load at peak demand
Peak Consumption Watts
Provides the peak power demand on the rPDU with
time
and date stamp of the most recent data update
Cumulative kWh Consumption
Provides the total kWh usage with
time and date stamp
of the most recent data update
NOTE:
This value accumulates. If this value reaches the
maximum value for a 32-bit number, do not reset.
Environment
No sensors connected
Displays dashes on both Temperature and Humidity
screens.
Only Temperature sensor connected
Displays the temperature in °C on the Temperature
screen. Displays dashes on the Humidity screen.
Temperature and Humidity sensors
connected
Displays the temperature in °C on the Temperature
screen. Displays the humidity percentage on the
Humidity screen.
Measured and Calculated Meters
The rPDU operating status information provided by the Performance menu selections is derived from a series of
measured and calculated meters. See Table 9 for descriptions of measured and calculated meters.
Table 9. Measured and Calculated Meters
Meter
Unit
Description
Input Voltage
Volts (V)
Present voltage measured at the 3
f input of the rPDU
Input Frequency
Hertz (Hz)
Present frequency measured at the input of the rPDU
Input Current
Amps (A)
Present current measured at 3
f input of the rPDU
Input Watts
Watts (W)
Calculated value of the overall input W of the rPDU (active power)
Input Volt-amperes
Volt-amperes (VA)
Calculated value of the overall input VA of the rPDU (apparent power)
Instantaneous Headroom
Watts
Watts (W)
Present W capacity remaining for the rPDU
NOTE:
This value is an absolute value calculated from the W rating of
rPDU deducted from the W being consumed.
Peak Headroom Watts
(with time stamp)
Watts (W)
Remaining W available to support the load at peak demand
NOTE:
This value is based on the lowest value set for that Instantaneous
Headroom Watts. The value can be reset from the LCD or the internal
Dell Network Management Card (NMC).