Appendix d, Modbus addresses (sc-2124m only) – Dynalco SC-2124M Scanner/Monitor User Manual

Page 69

background image

68

APPENDIX D


Modbus Addresses

(SC-2124M Only)


These addresses are all RUN time related (Function Code 03)

RANGE

CHANNELS

VALUE

INTEGER

DECIMAL


40001–40024

1-24

Scanner value (such as 327ºF)

X

40025

~

Channel number of first out

X

40026–40049

1-24

Alarm status (Alarmed or inactive)

X

40050–40073

1–24

Shutdown status (Alarmed or inactive)

X

40074–40097

1–24

Shutdown trip threshold

X

40098–40121

1–24

Alarm trip thresholds

X

40122–40137

User trips 1–16

User trip thresholds

X

47001–47024

1 - 24

Scanner value such (as 327ºF)

X

47025

1–24

Channel

number

of

first

out

X

47026–47049

Alarm status (Alarmed or inactive)

X

47050–47073

1–24

Shutdown status (Alarmed or inactive)

X

47074–47097

1–24

Shutdown

trip

threshold

X

47098–47121

1–24

Alarm

trip

thresholds

X

47124–47137

User trips 1–16

User trip thresholds

X



Parameter 2320 = 33309

To initiate the Modbus table


Parameter 2321 = Node #

(1 to 247)



See page 8 for wiring.