46

Channel 20 Input Settings

P a r a m e t e r

F u n c t i o n D e s c r i p t i o n

V a l i d I n p u t s

110.20=

Channel name for CH20

Default=” “

(blank=CH20)

11 characters (including spaces)

111.20=

Units of measure for CH20

0= deg F (default)
1= deg C
2= PSI
3= PSA
4= KPA
5= FTP
6= RPM
7= “ “ (blank)

8001.20=

Input type for CH20

0= J-TC (default)
1= K-TC
2= Nickel RTD
3= Platinum RTD
4= 4-20 mA (ext. resistor req’d)
5= 0-5 V

8000.20=

Enables CH20 for scanning

0= disabled (default)

1= enabled

8017.20=

Filter speed for CH20

Minimum=0.00 (none)
Default=0.05 (slow)
Maximum=1.00 (fast)

8012.20=

Display value for 0 V or 4 mA input

Minimum=-999.0

8013.20=

Output value for 5 V or 20 mA input

Default=

0.0

Maximum=9999.0
(in channel units)

8015.20=

Inverted resistance for 4-20mA source on CH20

Minimum=0.0 1/kohms
Default=10.0 1/kohms
Maximum=100.0 1 /kohms

8008.20=

CH20 output offset to add to computed output value

Minimum=-1000.0
Default= 0.0
Maximum= 1000.0
(in channel units)

63000.20=

Shutdown trip class for CH20

0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under

63001.20=

Shutdown threshold value for CH20

Numeric value

63002.20=

Shutdown threshold hystersis for CH20

(channel units)

63003.20=

Delay time between exceeded CH20 shutdown threshold and
CH20shutdown

seconds

63000.44=

Alarm trip class for CH20

0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under

63001.44=

Alarm threshold value for CH20

Numeric value

63002.44=

Alarm threshold hysteresis for CH20

(channel units)

63003.44=

Delay time between exceeded CH20 alarm threshold and
CH20 alarm

seconds