Channel 12 input settings – Dynalco SC-2124M Scanner/Monitor User Manual

Page 38

background image

38

Channel 12 Input Settings

P a r a m e t e r

F u n c t i o n D e s c r i p t i o n

V a l i d I n p u t s

110.12=

Channel name for CH12

Default=” “

(blank=CH12)

11 characters (including spaces)

111.12=

Units of measure for CH12

0= deg F (default)
1= deg C
2= PSI
3= PSA
4= KPA
5= FTP
6= RPM
7= “ “ (blank)

8001.12=

Input type for CH12

0= J-TC (default)
1= K-TC
2= Nickel RTD
3= Platinum RTD
4= 4-20 mA (ext. resistor req’d)
5= 0-5 V

8000.12=

Enables CH12 for scanning

0= disabled (default)

1= enabled

8017.12=

Filter speed for CH12

Minimum=0.00 (none)
Default=0.05 (slow)
Maximum=1.00 (fast)

8012.12=

Display value for 0 V or 4 mA input

Minimum=-999.0

8013.12=

Display value for 5 V or 20 mA input

Default=

0.0

Maximum=9999.0
(in channel units)

8015.12=

Inverted resistance for 4-20mA source on CH12

Minimum=0.0 1/kohms
Default=10.0 1/kohms
Maximum=100.0 1 /kohms

8008.12=

CH12 output offset to add to computed output value

Minimum=-1000.0
Default= 0.0
Maximum= 1000.0
(in channel units)

63000.12=

Shutdown trip class for CH12

0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under

63001.12=

Shutdown threshold value for CH12

Numeric value

63002.12=

Shutdown threshold hystersis for CH12

(channel units)

63003.12=

Delay time between exceeded CH12 shutdown threshold and
CH12shutdown

seconds

63000.36=

Alarm trip class for CH12

0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under

63001.36=

Alarm threshold value for CH12

Numeric value

63002.36=

Alarm threshold hysteresis for CH12

(channel units)

63003.36=

Delay time between exceeded CH12 alarm threshold and
CH12 alarm

seconds