/*$PAGE*/
; ************ AI DELAY TIMERS ************

; CHANNEL READ DLY TIME *******************
; Dly time between analog sw setup & analog
; read.
;
; Min Val Max Val
; 0.050 (dflt) -> 10.0 (in secs)
8200=0.050

; OPEN TC DETECT DLY TIME *****************
; Dly time between Open TC detections on
; consecutive TC channels.
;
; Min Val Max Val
; 0.1 -> 1.0 (dflt) -> 300.0 (in secs)
8201=1

; CJC UPDATE DLY TIME *********************
; Dly time between consecutive CJC reads.
;
; Min Val Max Val
; 5.0 -> 60.0 (dflt) -> 300.0 (in secs)
8202=60

; ************ AI CALIBRATION ************

; LOW CALIBRATION VOLTAGE INVERTED *******
; Min Val Max Val
; 0.0 (dflt) 1.0 -> 100.0 (in 1/V)
8101=43.88

; HIGH CALIBRATION VOLTAGE INVERTED *******
; Min Val Max Val
; 0.0 (dflt) 0.1 -> 2.0 (in 1/V)
8102=1.0

; NUMBER CALIBRATION AVERAGES *************
; Number of Calibration reads to perform
; and average for each AI offset and gain.
;
;
; Min Val Max Val
; 1 -> 10 (dflt) -> 255 (in iterations)
8152=10



; ********** CJC FILTER CONSTANT **********
; CJC Average Correction Filter.
;
; CJC = [CJC_prev * (1 - filter)] + [CJC_read * filter]
;
; Min Val Max Val
; 0.0 (dflt) -> 1.0 (no units)
100=0.1