Channel 4 input settings – Dynalco SC-2124M Scanner/Monitor User Manual

Page 30

background image

30

Channel 4 Input Settings

P a r a m e t e r

F u n c t i o n D e s c r i p t i o n

V a l i d I n p u t s

110.4=

Channel name for CH04

Default=” “

(blank=CH04)

11 characters (including spaces)

111.4=

Units of measure for CH04

0= deg F (default)
1= deg C
2= PSI
3= PSA
4= KPA
5= FTP
6= RPM
7= “ “ (blank)

8001.4=

Input type for CH04

0= J-TC (default)
1= K-TC
2= Nickel RTD
3= Platinum RTD
4= 4-20 mA (DIP 4 switch on)
5= 0-5 V

8000.4=

Enables CH04 for scanning

0= disabled (default)

1= enabled

8017.4=

Filter speed for CH04

Minimum=0.00 (none)
Default=0.05 (slow)
Maximum=1.00 (fast)

8012.4=

Display value for 0 V or 4 mA input

Minimum=-999.0

8013.4=

Display value for 5 V or 20 mA input

Default=

0.0

Maximum=9999.0
(in channel units)

8015.4=

Inverted resistance for 4-20mA source on CH04

Minimum=0.0 1/kohms
Default=10.0 1/kohms
Maximum=100.0 1 /kohms

8008.4=

CH04 output offset to add to computed output value

Minimum=-1000.0
Default= 0.0
Maximum= 1000.0
(in channel units)

63000.4=

Shutdown trip class for CH04

0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under

63001.4=

Shutdown threshold value for CH04

Numeric value

63002.4=

Shutdown threshold hystersis for CH04

(channel units)

63003.4=

Delay time between exceeded CH04 shutdown threshold and
CH04 shutdown

seconds

63000.28=

Alarm trip class for CH04

0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under

63001.28=

Alarm threshold value for CH04

Numeric value

63002.28=

Alarm threshold hysteresis for CH04

(channel units)

63003.28=

Delay time between exceeded CH04 alarm threshold and
CH04 alarm

seconds

This manual is related to the following products: