Channel 14 Input Settings

P a r a m e t e r

F u n c t i o n D e s c r i p t i o n

V a l i d I n p u t s

110.14=

Channel name for CH14

Default=” “

(blank=CH14)

11 characters (including spaces)

111.14=

Units of measure for CH14

0= deg F (default)
1= deg C
2= PSI
3= PSA
4= KPA
5= FTP
6= RPM
7= “ “ (blank)

8001.14=

Input type for CH14

0= J-TC (default)
1= K-TC
2= Nickel RTD
3= Platinum RTD
4= 4-20 mA (ext. resistor req’d)
5= 0-5 V

8000.14=

Enables CH14 for scanning

0= disabled (default)
1= enabled

8017.14=

Filter speed for CH14

Minimum=0.00 (none)
Default=0.05 (slow)
Maximum=1.00 (fast)

8012.14=

Display value for 0 V or 4 mA input

Minimum=-999.0

8013.14=

Display value for 5 V or 20 mA input

Default=

0.0

Maximum=9999.0
(in channel units)

8015.14=

Inverted resistance for 4-20mA source on CH14

Minimum=0.0 1/kohms
Default=10.0 1/kohms
Maximum=100.0 1 /kohms

8008.14=

CH14 output offset to add to computed output value

Minimum=-1000.0
Default= 0.0
Maximum= 1000.0
(in channel units)

63000.14=

Shutdown trip class for CH14

0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under

63001.14=

Shutdown threshold value for CH14

Numeric value

63002.14=

Shutdown threshold hystersis for CH14

(channel units)

63003.14=

Delay time between exceeded CH14 shutdown threshold and
CH14shutdown

seconds

63000.38=

Alarm trip class for CH14

0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under

63001.38=

Alarm threshold value for CH14

Numeric value

63002.38=

Alarm threshold hysteresis for CH14

(channel units)

63003.38=

Delay time between exceeded CH14 alarm threshold and
CH14 alarm

seconds