Appendix C

Channel 19 Input Settings

P a r a m e t e r

F u n c t i o n D e s c r i p t i o n

V a l i d I n p u t s

110.19=

Channel name for CH19

Default=” “

(blank=CH19)

11 characters (including spaces)

111.19=

Units of measure for CH19

0= deg F (default)
1= deg C
2= PSI
3= PSA
4= KPA
5= FTP
6= RPM
7= “ “ (blank)

8001.19=

Input type for CH19

0= J-TC (default)
1= K-TC
2= Nickel RTD
3= Platinum RTD
4= 4-20 mA (ext. resistor req’d)
5= 0-5 V

8000.19=

Enables CH19 for scanning

0= disabled (default)

1= enabled

8017.19=

Filter speed for CH19

Minimum=0.00 (none)
Default=0.05 (slow)
Maximum=1.00 (fast)

8012.19=

Display value for 0 V or 4 mA input

Minimum=-999.0

8013.19=

Display value for 5 V or 20 mA input

Default=

0.0

Maximum=9999.0
(in channel units)

8015.19=

Inverted resistance for 4-20mA source on CH19

Minimum=0.0 1/kohms
Default=10.0 1/kohms
Maximum=100.0 1 /kohms

8008.19=

CH19 output offset to add to computed output value

Minimum=-1000.0
Default= 0.0
Maximum= 1000.0
(in channel units)

63000.19=

Shutdown trip class for CH19

0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under

63001.19=

Shutdown threshold value for CH19

Numeric value

63002.19=

Shutdown threshold hystersis for CH19

(channel units)

63003.19=

Delay time between exceeded CH19 shutdown threshold and
CH19shutdown

seconds

63000.43=

Alarm trip class for CH19

0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under

63001.43=

Alarm threshold value for CH19

Numeric value

63002.43=

Alarm threshold hysteresis for CH19

(channel units)

63003.43=

Delay time between exceeded CH19 alarm threshold and
CH19 alarm

seconds