Cooper Instruments & Systems DFI Infinity CS Economy Digital Indicator User Manual
Page 19
![background image](/manuals/600669/19/background.png)
DFI INFINITY CS (V- M3598/N/0906)
16
CF 70
4.3.2 Scaling without Known Loads
To scale without known inputs, calculate input values based on transducer specifications and manually enter them
via the front-panel push buttons. The following example assumes load cells with these specifications:
Maximum
Load:
100.0
lbs
Output:
3.1
mV/V
Sensor Excitation:
10 Vdc
Output:
31 mV = (3.1 mV/V) x (10 V)
1. Determine the correct values for
and
, based on the load cell specifications. In most cases,
&
are equal to the minimum and maximum of the transducer output span. The example assumes
&
are equal to the range of the load
= 0 and
= 100.0). Calculate
and
using the
load cell output span and the following equation:
= (Sensor Output) x (Natural Gain) x (Multiplier).
Table 4-3 Natural Gain
Input range
Span units
Natural gain
0 to 100 mV
Millivolts
100 cts/mV
±50 mV
Millivolts
40 cts/mV
0 to 10 V
Volts
1000 cts/V
±5 V
Volts
400 cts/V
0 to 20 mA
Milliamps
500 cts/mA
2. Determine the multiplier by the Input Resolution setting (
in the
menu) and the input range selected.
Typically
is suitable for most applications.
Table 4-4 Input Resolution Multiplier
3. Determine
and
input range and resolution. The example selects the 0 to 100 mV range and 10 uV
resolution (
).
Example:
= (0 mV) x (100 cts/mV) x (1.000) =0
= (31 mV) x (100 cts/mV) x (1.000) = 3100
= 0000
= 100.0
4. Press
MENU button until the meter shows
.
5. Press
the
X/TARE button. The meter shows
.
6. Press
the
X/TARE button again. The meter shows the last Input 1 value, with the fourth digit flashing.
7. Press
the
S/NT/GRS button to change the value of your digits.
8. Press
the
X/TARE button to scroll horizontally to the next digit.
9. Press
the
MENU button to store this value. The meter shows
.
10. Press the
X/TARE button. The meter shows the last value for Read 1.
Repeat steps 7, 8 and 9 until
,
and
have been displayed, verified, changed (if necessary) and
stored.
4.4 Using Reading Configuration
Refer to Table 6-1 for a summary list of menu configuration.
INPUT RANGE
R.2 = 4
R.2 = 3
R.2 =2
R.2 = 1
R.2 =0
0
to
100
mV
1.000 2.000 3.333 5.000 10.00
0
to
10
V
1.000 2.000 3.333 5.000 10.00
0
to
20
mA
1.000 2.000 3.333 5.000 10.00
±50
mV
1.000 1.000 1.667 2.500 5.000
±5
V
1.000 1.000 1.667 2.500 5.000