Latch retraction exit device, Cno fire alarm system (dry contacts only) – SARGENT MPower 4000 User Manual
Page 15

80-9369-0901-021 (12-02 )
15
Electric Latch Retraction Exit Device Wiring
For Smoke Ventilation – Blow Open Function
56-
Latch Retraction Exit Device
Operation:
Doors are normally closed and latched.
Fire Alarm activation will retract the exit device
Latchbolt and the Door Operator will open the
door.
The door will remain open until the Fire Alarm
System has been reset.
The Door Operator’s main power input must be
wired into the buildings back-up power system.
Exit device allows egress at all times. Exit device
allows egress during power failure.
NOTE:
This application must be approved by local (AHJ)
authority having jurisdiction.
Notes:
1. Power input Door Operator Unit is at Power Input
Terminal Strip (not shown) 120VAC 60Hz.
2. Refer to Manufactures wiring instructions for Latch
Retraction Devices not shown.
3. Power Supply must be .900 Amps minimum per 56-
Latch Retraction Exit Device.
4. Set switch SW2 to position 3 for 1 second delay.
5
678
90
1
23
4
5
678
90
1
23
4
5
678
90
1
23
4
5
678
90
1
23
4
JP3
JP2
CL/AS DLY VEST DLY
EXSOL DLY
M. DLY
G
EM
G
H+
V
L
2
G
L1
MO
T
OR/SOLENOID
JP4
JP1
JP5
OFF
ON
SW1
P/A
A/D
RES1
RES2
0/0
RES1
A
UX2
GND
INV
OUTV
GND
R
F
T
GND
A
UX2
GND
PDET
GND
A
UX1
GND +24V NO1 CO1 NC1 NO2 CO2 NC2
NEU HOT GND
18VAC
1 2 3 4 5 6 7 8
14
13
12
11
10
9
8
7
6
5
4
3
2
1
C
NO
Fire Alarm System
(Dry Contacts Only)
(+)
(-)
120 VAC
24VDC
Filtered and Regulated
Power Supply
*See Note 3
RED
BLACK
-24VDC
+24VDC