beautypg.com

Carrier FLOTRONIC II 30GN040-420 User Manual

Page 52

background image

The voltage supplied to the processor is polarized. When

checking for proper voltage supply, be sure to consider this
polarity. If voltage appears to be within acceptable toler-
ance, check to be sure the transformer supplying PS1 is not
grounded. Grounding the supply transformer can result in
serious damage to the control system.
Code 29

LOCAL/ENABLE-STOP-CCN Switch Failure

(switch resistances out of range) (alarm)

This fault occurs due to the failure of the switch or due to

a wiring error.
Code 30

Reset input failure (4 to 20 mA) (alert)

Code 31

Demand limit input failure (4 to 20 mA) (alert)

These codes apply only if unit is configured for these func-

tions. If 4 to 20 mA signal is less than 4 or more than
20 mA, reset or demand limit function is disabled and unit
functions normally. If mA signal returns to the acceptable
range, function is automatically enabled.
Code 32

Loss of communication with compressor
relay module (DISO-LV) (alarm)

Code 33

Loss of communication with EXV relay
module (DSIO-EXV) (alarm)

If communication is lost with either of these modules, unit

shuts down without pumpout. This alarm resets automati-
cally when communication is restored. The unit starts up nor-
mally after alarm condition is reset. Probable cause of con-
dition is a faulty or improperly connected plug, wiring error,
or faulty module.

Loss of communication can be attributed to a grounded

transformer with a secondary voltage of 21 vac supplying
the PSIO, DSIO-LV, or 4 IN/4 OUT modules; the 12.5-vac
transformer supplying the DSIO-EXV module; or the
24-vac transformer supplying PS1 for the transformers. These
transformers should not be grounded, or serious damage to
controls can result.
Check to be sure the transformers are
not grounded.
NOTE: If a blank PSIO module is downloaded without be-
ing connected to the modules DSIO, this alarm is
energized.
Code 34

Loss of communication with 4 In/4 Out module

(alarm)

This applies only if one or more of the following options

are used:
• external temperature reset
• 4 to 20 mA temperature reset
• external switch controlled dual set point
• switch controlled demand limit
• 4 to 20 mA demand limit
• hot gas bypass

If communication is lost with 4 IN/4 OUT module, the

unit shuts off automatically, after finishing pumpout. Reset
of alarm is automatic when communication is restored. Start-up
after alarm is remedied follows a normal sequence. Probable
cause of condition is a faulty or improperly connected plug,
wiring error, or faulty module.

LEGEND

C

Contactor

CB

Circuit Breaker

COMM — Communications Bus
CPCS

Compressor Protection Control Module

DGT

Discharge Gas Thermostat (Optional)

DSIO

Relay Module (Low Voltage)

HPS

High-Pressure Switch

LV

Low Voltage

PL

Plug

PWR

Power

TB

Terminal Block

TRAN

Transformer

U

Unloader

*And associated modular units.

Fig. 11B — 24-V Safety Circuit Wiring (080-110 and Associated Modular Units)

52