Table 13 — Factory Configuration Keystrokes

To change a configuration enter the new configuration

and press

while on the correct configuration.

SUB-

KEYPAD

DISPLAY

COMMENTS

FUNCTION

ENTRY

3 FACTORY

CFG

FACT CFG

FACTORY

CONFIGURATION

CODES

XXXXXXXX

Configuration
Code 1

XXXXXXXX

Configuration
Code 2

XXXXXXXX

Configuration
Code 3

XXXXXXXX

Configuration
Code 4

XXXXXXXX

Configuration
Code 5

XXXXXXXX

Configuration
Code 6

XXXXXXXX

Configuration
Code 7

5 SERVICE

CFG

SRV CFG

SERVICE

CONFIGURATION

CODES

XXXXXXXX

Configuration
Code 8

XXXXXXXX

Configuration
Code 9

REFRIG X

Refrigerant Type

TDTYPE X

Pressure Transducer Select

OPS X

Oil Pressure Set Point

LPS X

Low Pressure Set Point

FANTYP X

Fan Staging Select

SH X

EXV Superheat Set Point

MOP X

EXV MOP Superheat

ZM X

Z Multiplier

LEGEND

MOP — Maximum Operating Pressure
EXV

Electronic Expansion Valve

When unit is configured for dual set point, chilled liquid

pump relay is energized continuously, in both occupied and
unoccupied modes. Occupied mode places occupied chilled
water set point into effect; unoccupied mode places unoc-
cupied chilled water set point into effect.

Scheduling —

is used to override any current sched-

ule in effect (for 0-4 hours).

is used to activate a

clock for the scheduling function.

-

are used

to program schedules for specific occupied and unoccupied
periods.

The schedule consists of from one to 8 occupied time pe-

riods, set by the operator. These time periods can be flagged
to be in effect or not in effect on each day of the week. The
day begins at 00.00 and ends at 24.00. The machine is in
unoccupied mode unless a scheduled time period is in effect.
If an occupied period is to extend past midnight, it must be
programmed in the following manner: occupied period must
end at 24:00 hours (midnight); a new occupied period must
be programmed to begin at 00:00 hours.

Table 14 — Adjustable Field Configurations

FIELD CONFIGURATION

ITEM AND CODES

FACTORY

SERVICE

CONFIGURATION

REPLACEMENT

CODE

CODE

CCN element address
(Entered by CCN Technician)

001

001

CCN Bus Number
(Entered by CCN Technician)

000

000

CCN Baud Rate
(Entered by CCN Technician)

9600

9600

Cooler Fluid Select
1 = Water (38 to 70 F

[3.3 to 21 C] Set Point)

2 = Medium Brine (15 to 70 F

[–9 to 21 C] Set Point)

1 = Standard Models

2 = Brine Models

1

Display Unit Select
0 = English
1 = Metric SI

0

0

Delay at Power Up

0

0

No. Circuit A Unloaders
0 = No Unloaders
1 = One Unloader
2 = Two Unloaders

0 = 30GN190-210*
1 = 30GN040-170*

0

No. Circuit B Unloaders
0 = No Unloaders
1 = One Unloader
2 = Two Unloaders

0 = 30GN040-070,

190-210*

1 = 30GN080-170*

0

Hot Gas Bypass Select
0 = No Valve

0

0

Loading Sequence Select
1 = Equal Circuit Loading
2 = Staged Circuit Loading

1

1

Lead/Lag Sequence Select
1 = Automatic
2 = Manual, Circuit A Leads
3 = Manual, Circuit B Leads

1

1

Oil Pressure Switch Select
0 = Not Used
1 = Air Cooled

0

0

Head Pressure Control Type
0 = Not Used
1 = Air Cooled

1

0

Head Pressure Control Method
1 = EXV Controlled
2 = Set Point Control for

Both Circuits

3 = Set Point Control for

Circuit A; EXV Control
for Circuit B

4 = Set Point Control for

Circuit B; EXV Control
for Circuit A

1

2 = 040,045

Brine Units

1

Motormaster

Select

0 = None
2 = Indirect Control

0

0

Cooling Set Point
Control Select
0 = Single Set Point Control
1 = External Switch

Controlled Set Point

2 = Clock Controlled

Set Point

0

0

Cooling Reset Control Select
0 = No Reset
1 = 4-20 mA, Internally Powered
2 = External Temperature

Reset

3 = Return Fluid Reset
4 = 4-20 mA, Externally Powered

0

0

External Reset Sensor Select
0 = Thermistor Connected to

Options Module

1 = Obtained Through CCN

0

0

Outdoor-Air Sensor Select
0 = Not Selected
1 = Selected

0

0

Demand Limit Control Select
0 = No Demand Limiting
1 = Two External Switch Inputs
2 = Internal 4-20 mA Input
3 = CCN Loadshed
4 = External 4-20 mA Input

0

0

Ramp Load Select
(Pulldown Control)
0 = Disabled
1 = Enabled

1

0

Cooler Pump Interlock Select
0 = No Interlock
1 = With Interlock

1

0

Cooler Pump Control Select
0 = Not Controlled
1 = ON/OFF Controlled

1

0

Remote Alarm Option Select
0 = Not Selected
1 = Selected

0

0

Local/Enable-Stop-CCN
Switch Usage†
0 = Not Allowed
1 = Allowed

1

1

LEGEND

CCN — Carrier Comfort Network
EXV

Electronic Expansion Valve

*And associated modular units.
†For reset of alarms.