Table 16 — Alarm and Alert Codes

DISPLAY

ALARM

DESCRIPTION

ACTION TAKEN

CIRCUIT

RESET

PROBABLE CAUSE

OR

ALERT

BY CONTROL

PUMPDOWN METHOD

0

No Alarms or Alerts Exist

1

Alert

Compressor A1 failure

Circuit A shut down

No

Manual

High-pressure switch trip, or wiring
error.

2, 3, 4

Compressor A2, A3, A4 failure

Compressor shut down

Yes

Manual

CPCS Ground Fault Protection

5

Compressor B1 failure

Circuit B shut down

No

Manual

6, 7, 8

Compressor B2, B3, B4 failure

Compressor shut down

Yes

Manual

9

Alarm

Leaving fluid thermistor failure

Unit shut down

Yes

Auto.

Thermistor or transducer failure
or wiring error.

10

Entering fluid thermistor failure

Unit shut down

Yes

Auto.

19

Alert

Compressor A1 sensor failure

Circuit A shut down

Yes

Auto.

20

Compressor B1 sensor failure

Circuit B shut down

Yes

Auto.

21

Reset thermistor failure

Normal set point used

No

Auto.

22

Alert

Discharge pressure transducer failure, circuit A Circuit A shut down

Yes

Auto.

Transducer failure or wiring error.

23

Discharge pressure transducer failure, circuit B Circuit B shut down

Yes

Auto.

24

Suction pressure transducer failure, circuit A

Circuit A shut down

No

Auto.

25

Suction pressure transducer failure, circuit B

Circuit B shut down

No

Auto.

26

Oil pressure transducer failure, circuit A

Circuit A shut down

No

Auto.

27

Oil pressure transducer failure, circuit B

Circuit B shut down

No

Auto.

28

Alarm

Transducer supply voltage low

Unit shut down

No

Auto.

Unit voltage low or PS1 faulty.

29

LOCAL/ENABLE-STOP-CCN

Unit shut down

No

Manual

Switch failure or wiring error.

30

Alert

4-20 mA reset input failure

Normal set point used

No

Auto.

31

4-20 mA demand limit failure

Demand limit ignored

No

Auto.

32

Alarm

Loss of communication with DSIO-LV

Unit shut down

No

Auto.

Wiring error or faulty module
or improper address code.

33

Loss of communication with DSIO-EXV

Unit shut down

No

Auto.

34

Loss of communication with 4 In/4 Out module

Unit shut down

Yes

Auto.

35

Not used

36

Alert

Low refrigerant pressure circuit A

Circuit A shut down

No

*

Low refrigerant charge, plugged filter
drier, faulty expansion valve.

37

Low refrigerant pressure circuit B

Circuit B shut down

No

*

Low refrigerant charge, plugged filter
drier, faulty expansion valve.

38

Alert

Failure to pump out circuit A

Circuit A shut down

No

Manual

Faulty expansion valve, transducer,
or thermistor.

39

Failure to pump out circuit B

Circuit B shut down

No

Manual

Faulty expansion valve, transducer,
or thermistor.

40

Alert

Low oil pressure circuit A

Circuit A shut down

No

Manual

Low oil level, circuit breaker trip,
faulty expansion valve, crankcase
heater, or pressure transducer.

41

Low oil pressure circuit B

Circuit B shut down

No

Manual

Low oil level, circuit breaker trip,
faulty expansion valve, crankcase
heater, or pressure transducer.

42

Alarm

Cooler freeze protection

Unit shut down

No

*

Low fluid flow or faulty thermistor.

43

Low cooler fluid flow

Unit shut down

No

Manual

Chilled fluid pump failure
or faulty thermistor.

44

Alert

Low suction temperature circuit A

Circuit A shut down
after 10 minutes

No

Manual

Faulty expansion valve or thermistor.

45

Low suction temperature circuit B

Circuit B shut down
after 10 minutes

No

Manual

Faulty expansion valve or thermistor.

46

Alert

High suction superheat circuit A

Circuit A shut down

Yes

Manual

Low charge, faulty expansion valve or
thermistor, or plugged filter drier.

47

High suction superheat circuit B

Circuit B shut down

Yes

Manual

Low charge, faulty expansion valve or
thermistor, or plugged filter drier.

48

Alert

Low suction superheat circuit A

Circuit A shut down

Yes

Manual

Faulty EXV or thermistor.

49

Low suction superheat circuit B

Circuit B shut down

Yes

Manual

Faulty EXV or thermistor.

50

Alarm

Illegal configuration

Unit cannot start

Manual

Configuration error.

51

Initial configuration required

Unit cannot start

Manual

Configuration omitted.

52

Emergency stop by CCN command

Unit shut down

Yes

CCN

Network command.

53

Alarm

Cooler pump interlock failure

Unit shut down

No

Manual

Failure of cooler pump or controls

54

Cooler pump interlock failure

Unit shut down

No

Manual

Failure of cooler pump or controls

55

Cooler pump interlock failure

Cooler pump shut down

Manual

Failure of cooler pump relay or interlock

56

Alert

WSM communication failure

WSM forces removed

Auto.

Wiring fault or module failure

57

Alert

Calibration required for discharge pressure
transducer, circuit A

Circuit cannot start

Auto.

Transducer not calibrated

58

Calibration required for discharge pressure
transducer, circuit B

Circuit cannot start

Auto.

59

Calibration required for suction pressure
transducer, circuit A

Circuit cannot start

Auto.

60

Calibration required for suction pressure
transducer, circuit B

Circuit cannot start

Auto.

61

Calibration required for oil pressure
transducer, circuit A

Circuit cannot start

Auto.

62

Calibration required for oil pressure
transducer, circuit B

Circuit cannot start

Auto.