Example 5B — 4 to 20 mA and Internally or

Externally Powered Reset

In this example, the unit set point is reset from full load

at 4 mA to a maximum reset value of 10 F (5.5 C) at
20 mA. Internally powered 4 to 20 mA option is used in this
example.

NOTE: To use externally powered reset, when CRTYP

appears, press

so CRTYP 4 appears in the

display. The remainder of the information in the fol-
lowing example applies to either type of reset.

KEYPAD

ENTRY

DISPLAY

RESPONSE

COMMENTS

FLD CFG

CRTYP 0

Scroll past to reset type

CRTYP 1

Internally powered reset
selected

RESET

CRT1 0

Reset at 20 mA is 0

CRT1 10

Reset at 20 mA is 10

Example 5C — Using Return Fluid

Temperature Reset

KEYPAD

DISPLAY

COMMENTS

ENTRY

RESPONSE

FLD CFG

Field configuration
subfunction of
service function

CSPTYP X

Scroll past single/dual

CRTYP 0

Display shows no reset
type has been selected

CRTYP 3

Return fluid temperature
is selected and activated

RESET

Reset set points

Temperature Reset Based on External Temperature — If de-
sired, temperature reset can be based on an external tem-
perature, such as space or outdoor-air temperature. This re-
quires a thermistor (T10, Part No. 30GB660002) located in
the space or outdoor air and wired to terminals as follows
(also see Field Wiring section on page 69 and Fig. 6):

4 in/4 out Module — J7-15 and J7-16.

At the field configuration step, enter set points as de-

scribed in Examples 5A-5C on pages 39 and 40. Then

select external temperature reset by entering

when

CRTYP 0 appears. See Fig. 7.

Temperature Reset Based on 4-20 mA Signal— If desired,
temperature reset can be based on a 4-20 mA signal. For
proper connections, refer to Field Wiring section on
page 69 and Fig. 8.

At the field configuration step, select 4-20 mA reset by

entering

(internally powered) or

(externally pow-

ered) when CRTYP 0 appears. Then enter set points as de-
scribed previously in Examples 5A-C. See Fig. 8.

Subfunction displays demand limit set points.

Demand Limit, 2-Stage Switch Control — This control has
been designed to accept demand limit signals from a build-
ing load shedding control. The demand limit function pro-
vides for 2 capacity steps. The keypad is used to set the 2
demand limit set points, which range from 100 to 0% of ca-
pacity. Capacity steps are controlled by 2 field-supplied re-
lay contacts connected to the designated chiller terminals.
(See Field Wiring section on page 69 and Fig. 7.)